Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
203 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 72 Liebert SICE 7200
- Input and Holding - SSC
Controller System Control Cabinet - SSC
Liebert Products Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Output Voltage L1-L2 40001 1 V
Output Voltage L2-L3 40002 1 V
Output Voltage L3-L1 40003 1 V
Output Amps L1 40004 1 A
Output Amps L2 40005 1 A
Output Amps L3 40006 1 A
Power L1 40007 1 kW
Power L2 40008 1 kW
Power L3 40009 1 kW
Bypass Frequency 40010 1 10 Hz
Battery Voltage 40012 1 V
Battery Amperage 40013 1 A
Apparent Power L1 40014 1 kVA
Apparent Power L2 40015 1 kVA
Apparent Power L3 40016 1 kVA
% Load L1 40017 1 %
% Load L2 40018 1 %
% Load L3 40019 1 %
% Battery Charge 40020 1 %
Battery Temperature 40021 1 deg C
Battery Time Remaining 40022 1 Minutes
Communications 40289 1 Bit 0
Bypass Switch Open 40289 1 Bit 1
Output Switch Open 40289 1 Bit 2
Battery CB Open 40289 1 Bit 3
Manual Bypass Closed 40289 1 Bit 4
Bypass Absent 40289 1 Bit 5
Bypass Overvoltage 40289 1 Bit 6
Bypass Undervoltage 40289 1 Bit 7
Bypass Frequency Error 40289 1 Bit 8
Bypass Ph Rotation Error 40289 1 Bit 9
Bypass SCR Failure 40289 1 Bit 10
Bypass Off 40290 1 Bit 0
Bypass Off 40290 1 Bit 1
Load On Bypass 40290 1 Bit 2
Bypass Overtemperature 40290 1 Bit 3
Inverter Non Sync 40290 1 Bit 4
Output Overvoltage 40290 1 Bit 5
Output Undervoltage 40290 1 Bit 6