Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 44
Condenser Low Noise Mode Schedule Control 30491 40491 1
0 = disabled
1 = enabled
Condenser Low Noise Mode Max Fan Speed 30492 40492 1 %
Condenser Normal Mode Max Fan 30493 40493 1 %
Condenser Low Noise Mode - Interval Days 30494 40494 1
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode - Full Days 30495 40495 1
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode Start Time 30496 40496 2 Seconds since Midnight
Condenser Low Noise Mode Stop Time 30498 40498 2 Seconds since Midnight
System Event Acknowledge/Reset 40500 1
2 = Reset
4 = Acknowledge
System Date and Time 39998 49998 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 12 Liebert CRV
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units