Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 140
Table 51 Liebert Nfinity
®
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 — Bits 12 - 15
Number of Bypass Lines 30004 40004 1 — Bits 4 - 7
Number of Output Lines 30004 40004 1 — Bits 8 - 11
Number of Power Mod. 30010 40010 1 — —
Number of Battery Modules Installed 30011 40011 1 — —
Device Maximum Frame Capacity 30023 40023 2 — —
Device System Capacity 30025 40025 2 — VA
Nominal Input Voltage 30027 40027 1 — V
Nominal Output Voltage 30028 40028 1 — V
Nominal Static Bypass Switch Voltage 30029 40029 1 — V
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 —
Nominal Battery Voltage 30034 40034 1 — V
Auto Restart Delay 30051 40051 1 — Seconds
Device Auto Restart Percent Setpt 30052 40052 1 — %
Device Low Battery Time 30053 40053 1 — Minutes
Next Battery Auto Test Time 30057 40057 1 — Minutes
Overload Alarm Limit 30067 40067 2 — VA
Minimum Redundant Power Modules 30074 40074 1 — —
Load (Apparent Power) 30102 — 2 — VA
Load (Real Power) 30104 — 2 — W
Load / Capacity 30106 — 1 — %
Input Frequency 30107 — 1 10 Hz
Output Frequency 30108 — 1 10 Hz
Bypass Frequency 30109 — 1 10 Hz
Battery Charge Status 30112 — 1 —
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 — 1 — V
Battery Time Remaining 30115 — 1 — Minutes
Battery Charge Percentage 30116 — 1 — %
Battery Temperature 30117 — 1 — deg C
Transformer Temperature 30121 — 1 — deg C
Redundant Power Modules 30124 — 1 — —
Active Power Module Count 30126 — 1 — —
Battery Module Active Count 30127 — 1 — —
Battery Test Result 30130 — 1 — -
Input Voltage L1 30153 — 1 — V
Input Current L1 30154 — 1 — A
Bypass Voltage L1 30159 — 1 — V
Bypass Current L1 30160 — 1 — A
Output Voltage L1 30163 — 1 — V
Output Current L1 30164 — 1 — A
Power Module Failure Count 30304 — 1 — —
Battery Module Failure Count 30305 — 1 — —
Power Module Warning Count 30306 — 1 — —
Battery Module Warning Count 30307 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.