Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 294
Pump Hours Operating hours for pump since last reset of this value.
Pump Short Cycle - Event Control
Enable/disable the activation of the [Pump Short Cycle] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Pump Short Cycle - Event Type The event type for the [Pump Short Cycle] event.
Pump Short Cycle
Pumps have short cycled. A short cycle is defined as turning on and off a
number of times over a set time period.
RAM Battery Issue RAM or RAM backup battery is not operating correctly.
Remote Sensor Temperature Air temperature as measured by remote sensor.
Remote Shutdown Unit is shut down by a remote signal.
Sensor Issue - Event Control
Enable/disable the activation of the [Sensor Issue] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Sensor Issue - Event Type The event type for the [Sensor Issue] event.
Sensor Issue One or more sensors are disconnected or the signals are out of range.
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Service Required - Event Type The event type for the [Service Required] event.
Service Required Unit requires servicing.
Shutdown - Loss Of Power - Event Control
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Shutdown - Loss Of Power - Event Type The event type for the [Shutdown - Loss Of Power] event.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on
following an unexpected loss of power.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Smoke Detected - Event Type The event type for the [Smoke Detected] event.
Smoke Detected Smoke detected.
Supply Chilled Water Over Temp
Threshold
Threshold value used in the [Supply Chilled Water Over Temp] event.
Supply Chilled Water Over Temp
[Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over
Temp Threshold].
Supply Chilled Water Temp Sensor Issue
The supply chilled water temperature sensor is disconnected or the signal is
out of range.
Supply Chilled Water Temperature Supply chilled water temperature.
Supply CW Over Temp - Event Control
Enable/disable the activation of the [Supply Chilled Water Over Temp] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Supply CW Over Temp - Event Type The event type for the [Supply Chilled Water Over Temp] event.
Supply CW Temp Sensor Issue - Event
Control
Enable/disable the activation of the [Supply Chilled Water Temp Sensor Issue]
event. If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Supply CW Temp Sensor Issue - Event
Type
The event type for the [Supply Chilled Water Temp Sensor Issue] event.
Supply Fluid Over Temp - Event Control
Enable/disable the activation of the [Supply Fluid Over Temp] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Supply Fluid Over Temp - Event Type The event type for the [Supply Fluid Over Temp] event.
Table 95 Liebert XDP
, Liebert XDC
- Glossary (continued)
Data Label Data Description