Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
209 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 75 Alber
®
BDSU
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Battery Measurement and Control
System Status 30385 1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
Battery Entity
Battery Name
Battery 1 - 32
30386-31057 21
Each 16-bit register is a
single Unicode character of a
null terminated string
Battery Rating
Battery 1 - 32
31186-31217 1 Units : AH
Battery Time Remaining
Battery 1 - 32
31058-31121 2 Units : sec
Battery Discharge Time
Battery 1 - 32
31122-31185 2 Units : sec
Ordinal Position of Battery
Battery 1 - 32
31218-31249 1
String Entity
Battery String Name
String 1 - 32
31250-31921 21
Each 16-bit register is a
single Unicode character of a
null terminated string
Installation Date
String 1 - 32
33170-33233 2 Secs since Epoch(UTC)
Cell/Monobloc Rating
String 1 - 32
33234-33265 1 Units : AH
String Ambient Temperature 1
String 1 - 32
31922-31953 1
Scale
: x /
10
Units : deg C
String Ambient Temperature 2
String 1 - 32
31954-31985 1
Scale
: x /
10
Units : deg C
String Ambient Temperature 1
String 1 - 32
31986-32017 1
Scale
: x /
10
Units : deg F
String Ambient Temperature 2
String 1 - 32
32018-32049 1
Scale
: x /
10
Units : deg F
String Overall Voltage
String 1 - 32
32050-32081 1
Scale
: x /
10
Units : VDC
String Current
String 1 - 32
32082-32113 1 Units : A DC
Float Current
String 1 - 32
32114-32145 1 Units : mA DC
Ripple Current
String 1 - 32
32146-32177 1 Units : A AC
Total Active Alarms on a Battery String
String 1 - 32
32178-32209 1 Units : 0
Discharge State
String 1 - 32
32210-32241 1
0 = Not In Progress
1 = In Progress
Battery String Discharge Time
String 1 - 32
32338-32401 2 Units : sec