Modbus 485 and Modbus IP Protocols - Thermal Management Products
41 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 12 Liebert CRV
™
- Input and Holding
Controller Liebert iCOM
®
v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Supply Air Temperature 30385 — 1 10 deg C
Supply Air Temperature 30386 — 1 10 deg F
Return Air Temperature 30387 — 1 10 deg C
Return Air Temperature 30388 — 1 10 deg F
Return Dew Point 30389 — 1 10 deg C
Return Dew Point 30390 — 1 10 deg F
Remote Sensor Minimum Temperature 30391 — 1 10 deg C
Remote Sensor Minimum Temperature 30392 — 1 10 deg F
Remote Sensor Maximum Temperature 30393 — 1 10 deg C
Remote Sensor Maximum Temperature 30394 — 1 10 deg F
Remote Sensor Average Temperature 30395 — 1 10 deg C
Remote Sensor Average Temperature 30396 — 1 10 deg F
Air Temperature Set Point 30397 40397 1 10 deg C
Air Temperature Set Point 30398 40398 1 10 deg F
Cooling Proportional Band 30399 40399 1 10 deg C
Cooling Proportional Band 30400 40400 1 10 deg F
Heating Proportional Band 30401 40401 1 10 deg C
Heating Proportional Band 30402 40402 1 10 deg F
Air Temperature Dead Band 30403 40403 1 10 deg C
Air Temperature Dead Band 30404 40404 1 10 deg F
Supply Air Over Temp Threshold 30405 40405 1 10 deg C
Supply Air Over Temp Threshold 30406 40406 1 10 deg F
Supply Air Under Temp Threshold 30407 40407 1 10 deg C
Supply Air Under Temp Threshold 30408 40408 1 10 deg F
Return Air Over Temp Threshold 30409 40409 1 10 deg C
Return Air Over Temp Threshold 30410 40410 1 10 deg F
Supply Humidity 30411 — 1 10 % RH
Return Humidity 30412 — 1 10 % RH
Humidity Set Point 30413 40413 1 — % RH
Humidification Proportional Band 30414 40414 1 — % RH
Dehumidification Proportional Band 30415 40415 1 — % RH
Humidity Dead Band 30416 40416 1 — % RH
High Return Humidity Threshold 30417 40417 1 10 % RH
Low Return Humidity Threshold 30418 40418 1 10 % RH
Fan Speed Proportional Band 30419 40419 1 10 deg C
Fan Speed Proportional Band 30420 40420 1 10 deg F
Fan Speed Manual Set Point 30421 40421 1 — %
Fan Speed Maximum Set Point 30422 40422 1 — %
Fan Speed Minimum Set Point 30423 40423 1 — %
Remote Sensor Temperature Module Index 1 30424 — 1 10 deg C
Remote Sensor Temperature Module Index 2 30425 — 1 10 deg C
Remote Sensor Temperature Module Index 3 30426 — 1 10 deg C