Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 152
System Output Pct Power Phase A 30165 1 %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs A 30166 1 100
N+1, 1+N,
1+1, SMS
System Input RMS B-C 30201 1 VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase B 30204 1 A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS B-C 30207 1 VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS B-C 30211 1 VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS B-N 30212 1 VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs B 30214 1 A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase B 30215 1 %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs B 30216 1 100
N+1, 1+N,
1+1, SMS
System Input RMS C-A 30251 1 VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase C 30254 1 A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS C-A 30257 1 VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS C-A 30261 1 VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS C-N 30262 1 VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs C 30264 1 A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase C 30265 1 %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs C 30266 1 100
N+1, 1+N,
1+1, SMS
Battery Discharge Time 30309 1 sec
N+1, 1+N,
1+1, SMS
Battery Amp-Hours Consumed This
Discharge
30310 1 AH
N+1, 1+N,
1+1, SMS
Input Qualification Status 30312 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
Bypass Sync Phase Difference 30313 1 deg
SCC, 1+N,
1+1, SMS
Bypass SS Overload Time Remain 30314 1 sec
SCC, 1+N,
1+1, SMS
Bypass Qualification Status 30315 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
SCC, 1+N,
1+1, SMS
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types