Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 96
Table 34 Liebert Datawave
, Liebert FPC
, Liebert PPC
- Input and Holding - PMP Option for
Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Voltage In X-Y 40001 1 V
Voltage In Y-Z 40002 1 V
Voltage In Z-X 40003 1 V
Voltage Out A-B 40004 1 V
Voltage Out B-C 40005 1 V
Voltage Out C-A 40006 1 V
Voltage Out A-N 40007 1 V
Voltage Out B-N 40008 1 V
Voltage Out C-N 40009 1 V
Current Out A 40010 1 A
Current Out B 40011 1 A
Current Out C 40012 1 A
Ground Current 40013 1 10 A
Neutral Current 40014 1 A
kVA 40015 1 kVA
kW 40016 1 kW
Frequency 40017 1 10 Hz
% Capacity A 40018 1 %
% Capacity B 40019 1 %
% Capacity C 40020 1 %
Alarm Points
Discrete alarm objects available; use auto-
discover for this unit
Communications 40289 1 Bit 0
Output Undervoltage 40289 1 Bit 1
Output Overvoltage 40289 1 Bit 2
Output Overcurrent 40289 1 Bit 3
Frequency Deviation 40289 1 Bit 4
Ground Overcurrent 40289 1 Bit 5
Transformer Overtemp 40289 1 Bit 6
Ground Fault 40289 1 Bit 7
Ground Failure 40289 1 Bit 8
Liquid Detected 40289 1 Bit 9
Security Alarm 40289 1 Bit 10
Phase Rotation/Loss 40290 1 Bit 0
Datawave Overtemperature 40290 1 Bit 1
Emergency Shutdown 40290 1 Bit 2
Load On Bypass 40290 1 Bit 3
Local Alarm 40290 1 Bit 4
Custom Alarm #1 40290 1 Bit 5
Custom Alarm #2 40290 1 Bit 6
Setpoints (View)
None 1
Control Points (Set)
None 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.