Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 96
Table 34 Liebert Datawave
™
, Liebert FPC
™
, Liebert PPC
™
- Input and Holding - PMP Option for
Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Voltage In X-Y — 40001 1 — V
Voltage In Y-Z — 40002 1 — V
Voltage In Z-X — 40003 1 — V
Voltage Out A-B — 40004 1 — V
Voltage Out B-C — 40005 1 — V
Voltage Out C-A — 40006 1 — V
Voltage Out A-N — 40007 1 — V
Voltage Out B-N — 40008 1 — V
Voltage Out C-N — 40009 1 — V
Current Out A — 40010 1 — A
Current Out B — 40011 1 — A
Current Out C — 40012 1 — A
Ground Current — 40013 1 10 A
Neutral Current — 40014 1 — A
kVA — 40015 1 — kVA
kW — 40016 1 — kW
Frequency — 40017 1 10 Hz
% Capacity A — 40018 1 — %
% Capacity B — 40019 1 — %
% Capacity C — 40020 1 — %
Alarm Points
Discrete alarm objects available; use auto-
discover for this unit
Communications — 40289 1 — Bit 0
Output Undervoltage — 40289 1 — Bit 1
Output Overvoltage — 40289 1 — Bit 2
Output Overcurrent — 40289 1 — Bit 3
Frequency Deviation — 40289 1 — Bit 4
Ground Overcurrent — 40289 1 — Bit 5
Transformer Overtemp — 40289 1 — Bit 6
Ground Fault — 40289 1 — Bit 7
Ground Failure — 40289 1 — Bit 8
Liquid Detected — 40289 1 — Bit 9
Security Alarm — 40289 1 — Bit 10
Phase Rotation/Loss — 40290 1 — Bit 0
Datawave Overtemperature — 40290 1 — Bit 1
Emergency Shutdown — 40290 1 — Bit 2
Load On Bypass — 40290 1 — Bit 3
Local Alarm — 40290 1 — Bit 4
Custom Alarm #1 — 40290 1 — Bit 5
Custom Alarm #2 — 40290 1 — Bit 6
Setpoints (View)
None — 1 — —
Control Points (Set)
None — — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.