Modbus 485 and Modbus IP Protocols - UPS Systems
125 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Output
Output Overload 10050 — 1 Active on Alarm
Output Off Pending 10051 — 1 Active on Alarm
System Output Off 10052 — 1 Active on Alarm
System Shutdown - Transformer Over Temperature 10053 — 1 Active on Alarm
Inverter Shutdown - Overload 10054 — 1 Active on Alarm
System Shutdown - Output Short 10055 — 1 Active on Alarm
System Shutdown - Low Battery 10056 — 1 Active on Alarm
System Shutdown - Remote Shutdown 10057 — 1 Active on Alarm
System Shutdown - Hardware Fault 10058 — 1 Active on Alarm
Maximum Load Alarm 10059 — Active on Alarm
Inverter
Loss of Redundancy 10070 — 1 Active on Alarm
Power Module Failure 10071 — 1 Active on Alarm
Power Module Warning 10072 — 1 Active on Alarm
System Status
Unspecified General Event 10083 — 1 Active on Alarm
Check Air Filter 10084 — 1 Active on Alarm
Frame Fan Fault 10085 — 1 Active on Alarm
Transformer Fan Fault 10086 — 1 Active on Alarm
Transformer Overtemperature 10087 — 1 Active on Alarm
No Load Warning 10088 — 1 Active on Alarm
PowerModule 1
Power Module Fan Fault 10099 — 1 Active on Alarm
Power Module Over Temperature 10100 — 1 Active on Alarm
Power Module Shutdown - Over Temperature 10101 — 1 Active on Alarm
PowerModule 10
Power Module Fan Fault 10216 — 1 Active on Alarm
Power Module Over Temperature 10217 — 1 Active on Alarm
Power Module Shutdown - Over Temperature 10218 — 1 Active on Alarm
BatteryModule 1
Battery Module Temperature Sensor Fault 10229 — 1 Active on Alarm
Battery Module Over Temperature 10230 — 1 Active on Alarm
Replace Battery Module 10231 — 1 Active on Alarm
BatteryModule 2
Battery Module Temperature Sensor Fault 10242 — 1 Active on Alarm
Battery Module Over Temperature 10243 — 1 Active on Alarm
Replace Battery Module 10244 — 1 Active on Alarm
BatteryModule 80
Battery Module Temperature Sensor Fault 11256 — 1 Active on Alarm
Battery Module Over Temperature 11257 — 1 Active on Alarm
Replace Battery Module 11258 — 1 Active on Alar
ChargerModule
Charger Module Fan Fault 11269 — 1 Active on Alarm
Table 43 Liebert APS
™
- Status and Coil (continued)
Data Label
Status Coil
Number
of Bits Notes