Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 236
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Multistate Data
Data Label Object Type Instance Object Name Access Notes
Extra
Notes
Protocol
Server Class MultiState_Value 1 4553_1 RD
1 = UPS
2 = AIR
3 = PMP
4 = PDU
1, 2, 3,
4, 5, 6
Air
Air Temperature Control Type MultiState_Value 12 5324_1 RW
1 = Proportional
2 = Prop+Integral
3 = Intelligent
1, 2, 3,
4, 5, 6
Air Temperature Control Sensor MultiState_Value 13 5012_1 RW
1 = Supply
2 = Remote
3 = Return
2, 3, 4,
5, 6
Air - Supply Air
Supply Air Temperature Sensor
Control
MultiState_Value 23 5332_1_1 RW
1 = Disabled
2 = Limit
3 = Control
4 = Temp Only
1
Humidity
Humidity Proportional Control
Type
MultiState_Value 34 5340_1 RW
1 = Relative
2 = Compensated
3 = Predictive
1
Humidity Proportional Control
Type
MultiState_Value 35 5603_1 RW
1 = Relative
2 = Compensated
3 = Predictive
4 = Dew Point
2, 3, 4,
5, 6
Humidity Control Sensor MultiState_Value 36 5618_1 RW
1 = Supply
2 = Remote
3 = Return
3, 4, 5,
6
Compressors - Compressor 1
Fixed Compressor State MultiState_Value 45 5264_1_1 RD
1 = off
2 = on
1, 2, 3,
4, 5, 6
Compressor Capacity Control
State
MultiState_Value 46 5265_1_1 RD
1 = off
2 = on
1, 2, 3,
4, 5, 6
Compressors - Compressor 2
Fixed Compressor State MultiState_Value 57 5264_1_2 RD
1 = off
2 = on
1, 2, 3,
4, 5, 6
Compressor Capacity Control
State
MultiState_Value 58 5265_1_2 RD
1 = off
2 = on
1, 2, 3,
4, 5, 6
Free Cooling / Chilled Water
Free Cooling Status MultiState_Value 69 5302_1 RD
1 = off
2 = on
3 = No Support
1, 2, 3,
4, 5, 6
Free Cooling Internal Control
Mode
MultiState_Value 70 5581_1 RW
1 = Disabled
2 = Contact
3 = Temperature
4 = Set Point
2, 3, 4,
5, 6
Minimum Chilled Water Temp
Set Point Enable
MultiState_Value 71 5359_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Main Chilled Water Valve MultiState_Value 72 5605_1 RW
1 = Valve 1
2 = Valve 2
2, 3, 4,
5, 6
Fan