Modbus 485 and Modbus IP Protocols - UPS Systems
143 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 53 Liebert NX
™
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 — Bits 12 - 15
Number of Bypass Lines 30004 40004 1 — Bits 4 - 7
Number of Output Lines 30004 40004 1 — Bits 8 - 11
Number of SubModules 30009 40009 1 — —
Module Number 30014 40014 1 — —
Device Module Count 30015 40015 1 — —
Device Redundant Count 30016 40016 1 — —
Device Module Mode 30017 40017 1 — —
Nominal Power Rating 30021 40021 2 — VA
Nominal Input Voltage 30027 40027 1 — V
Nominal Output Voltage 30028 40028 1 — V
Nominal Static Bypass Switch Voltage 30029 40029 1 — V
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 —
Nominal DC Bus #1 Voltage 30035 40035 1 — V
Nominal DC Bus #2 Voltage 30036 40036 1 — —
Nominal Battery Float Voltage 30038 40038 1 — V
Load Bus Sync Mode 30040 40040 1 — —
Auto Restart Delay 30051 40051 1 — Seconds
Device Low Battery Time 30053 40053 1 — Minutes
Input Frequency 30107 — 1 10 Hz
Output Frequency 30108 — 1 10 Hz
Bypass Frequency 30109 — 1 10 Hz
Battery Charge Status 30112 — 1 —
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 — 1 — V
Battery Current (Charge/Discharge) 30114 — 1 — A
Battery Time Remaining 30115 — 1 — Minutes
Battery Charge Percentage 30116 — 1 — %
Battery Temperature 30117 — 1 — C
Ambient Temperature 30119 — 1 — C
Parallel Load Source 30128 — 1 — —
Rotary Breaker 30129 — 1 — —
Battery Test Result 30130 — 1 —
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2 30151 — 1 — V
Input Voltage L1 30153 — 1 — V