Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
285 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Compressors
Compressor 1A State Multistate_Value 91 4665_1 RD 1 = Off / 2 = On
Compressor 1B State Multistate_Value 92 4666_1 RD 1 = Off / 2 = On
Compressor 2A State Multistate_Value 93 4667_1 RD 1 = Off / 2 = On
Compressor 2B State Multistate_Value 94 4668_1 RD 1 = Off / 2 = On
Compressor 1A High Head Pressure - Event
Control
Multistate_Value 95 4670_1 RW
1 = Disabled
2 = Enabled
Compressor 1A High Head Pressure - Event
Type
Multistate_Value 96 4671_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1B High Head Pressure - Event
Control
Multistate_Value 97 4673_1 RW
1 = Disabled
2 = Enabled
Compressor 1B High Head Pressure - Event
Type
Multistate_Value 98 4674_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2A High Head Pressure - Event
Control
Multistate_Value 99 4676_1 RW
1 = Disabled
2 = Enabled
Compressor 2A High Head Pressure - Event
Type
Multistate_Value 100 4677_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2B High Head Pressure - Event
Control
Multistate_Value 101 4679_1 RW
1 = Disabled
2 = Enabled
Compressor 2B High Head Pressure - Event
Type
Multistate_Value 102 4680_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1A Short Cycle - Event Control Multistate_Value 103 4682_1 RW
1 = Disabled
2 = Enabled
Compressor 1A Short Cycle - Event Type Multistate_Value 104 4683_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 1B Short Cycle - Event Control Multistate_Value 105 4685_1 RW
1 = Disabled
2 = Enabled
Compressor 1B Short Cycle - Event Type Multistate_Value 106 4686_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2A Short Cycle - Event Control Multistate_Value 107 4688_1 RW
1 = Disabled
2 = Enabled
Compressor 2A Short Cycle - Event Type Multistate_Value 108 4689_1 RW
1 = Message
2 = Warning
3 = Alarm
Compressor 2B Short Cycle - Event Control Multistate_Value 109 4691_1 RW
1 = Disabled
2 = Enabled
Compressor 2B Short Cycle - Event Type Multistate_Value 110 4692_1 RW
1 = Message
2 = Warning
3 = Alarm
Circuit 1 Low Suction Pressure - Event Control Multistate_Value 111 4694_1 RW
1 = Disabled
2 = Enabled
Circuit 1 Low Suction Pressure - Event Type Multistate_Value 112 4695_1 RW
1 = Message
2 = Warning
3 = Alarm
Circuit 2 Low Suction Pressure - Event Control Multistate_Value 113 4697_1 RW
1 = Disabled
2 = Enabled
Table 94 Liebert XDP
, Liebert XDC
- Multistate Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes