Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 138
Output Current L1 30164 1 A
Input Maximum Voltage L1 30180 1 V
Input Minimum Voltage L1 30181 1 V
Output Maximum Voltage L1 30182 1 V
Output Minimum Voltage L1 30183 1 V
Black Out Count 30301 1
Brown Out Count 30302 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 48 Liebert HiNet
- Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
DC-To-DC Converter On 10042 1
Load On Inverter 10073 1
Bypass Active 10074 1
Load On Battery 10128 1
Permanently On Bypass 10133 1
Bypass SCR Open Circuit 10149 1
Low Battery - Shutdown Imminent 10152 1
Output Overload 10154 1
Inverter Unsynchronized 10160 1
Input Power Supply Fail 10186 1
Bypass Input Voltage/Frequency Fault 10202 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 49 Liebert HiNet - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 Bits 8 - 11
Number of SubModules 30009 40009 1 -
Number of Battery Cells 30012 40012 1 -
Load (Apparent Power) 30102 2 VA
Load (Real Power) 30104 2 W
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Battery Voltage 30113 1 V
Battery Current (Charge/Discharge) 30114 1 A
Battery Charge Percentage 30116 1 %
Ambient Temperature 30119 1 deg C
Input Voltage L1 30153 1 V
Input Current L1 30154 1 A
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Input Voltage L2 30203 1 V
Input Current L2 30204 1 A
Input Voltage L3 30253 1 V
Input Current L3 30254 1 A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 47 Liebert GXT2
and Liebert GXT3
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units