Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 30
Ext Air Sensor A High Humidity
Threshold
Threshold value used in the [External Air Sensor A High Humidity] event.
Ext Air Sensor A High Humidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
Ext Air Sensor A Humidity Relative humidity as measured by external air sensor A.
Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Low Humidity -
Event Control
Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Air Sensor A Low Humidity -
Event Type
The event type for the [Ext Air Sensor A Low Humidity] event.
Ext Air Sensor A Low Humidity
Threshold
Threshold value used in the [External Air Sensor A Low Humidity] event.
Ext Air Sensor A Low Humidity
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity
Threshold].
Ext Air Sensor A Over Temp -
Event Control
Enable/disable the activation of the [External Air Sensor A Over Temperature] event. If
set to 'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Air Sensor A Over Temp -
Event Type
The event type for the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over Temp
Threshold
Threshold value used in the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over
Temperature
[Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp
Threshold].
Ext Air Sensor A Temperature Air temperature as measured by external air sensor A.
Ext Air Sensor A Under Temp -
Event Control
Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Air Sensor A Under Temp -
Event Type
The event type for the [Ext Air Sensor A Under Temperature] event.
Ext Air Sensor A Under Temp
Threshold
Threshold value used in the [External Air Sensor A Under Temperature] event.
Ext Air Sensor A Under
Temperature
[Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp
Threshold].
Ext Air Sensor B Humidity Relative humidity as measured by external air sensor B.
Ext Air Sensor B Temperature Air temperature as measured by external air sensor B.
Ext Air Sensor C Humidity Relative humidity as measured by external air sensor C.
Ext Air Sensor C Temperature Air temperature as measured by external air sensor C.
Ext Compressor Lockout - Event
Control
Enable/disable the activation of the [Ext Compressor Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Compressor Lockout - Event
Type
The event type for the [Ext Compressor Lockout] event.
Ext Compressor Lockout The compressor is shut down and disabled by an external input signal.
Ext Condenser Pump High Water -
Event Control
Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Condenser Pump High Water -
Event Type
The event type for the [Ext Condenser Pump High Water] event.
Ext Condenser Pump High Water High water is detected in the condenser, as indicated by an external input signal.
Table 10 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Glossary (continued)
Controller Liebert iCOM
®
v4
Data Label Data Description