Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 112
Table 38 Liebert STS
, Liebert STS/PDU
- Input and Holding - STS
Controller STS
Liebert Products
Liebert STS
Liebert STS/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Transfer Count 40001 1
Preferred Source 40002 1 1=Source 1 / 2=Source 2
Load On Source 40003 1 1=Source 1 / 2=Source 2
Source 1 Voltage A-B 40004 1 V
Source 1 Voltage B-C 40005 1 V
Source 1 Voltage C-A 40006 1 V
Source 1 Current A 40007 1 A
Source 1 Current B 40008 1 A
Source 1 Current C 40009 1 A
Source 1 Frequency 40010 1 10 Hz
Source 2 Voltage A-B 40011 1 V
Source 2 Voltage B-C 40012 1 V
Source 2 Voltage C-A 40013 1 V
Source 2 Current A 40014 1 A
Source 2 Current B 40015 1 A
Source 2 Current C 40016 1 A
Source 2 Frequency 40017 1 10 Hz
kW 40018 1 kW
kVA 40019 1 kVA
Auto Transfer Timer 40020 1 Seconds
Nominal Voltage Deviation 40021 1 V
Phase Differential Limit 40022 1 Degree
Frequency Deviation 40023 1 10 Hz
Alarm Points
Communications 40289 1 Bit 0
Logic Failure 40289 1 Bit 1
Equipment Overtemp 40289 1 Bit 2
Power Supply 1 Fault 40289 1 Bit 3
Source 1 Overvoltage 40289 1 Bit 4
Source 1 Undervoltage 40289 1 Bit 5
Source 2 Overvoltage 40289 1 Bit 6
Source 2 Undervoltage 40289 1 Bit 7
Source 1 Overload 40289 1 Bit 8
Shorted SCR1 40289 1 Bit 9
Shorted SCR2 40289 1 Bit 10
Open SCR1 40290 1 Bit 0
Open SCR2 40290 1 Bit 1
Fan Failure 40290 1 Bit 2