Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 168
Table 58 Liebert NXL
- 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status Coil
Number
of Bits Notes / Units
Input
System Input Power Problem 10001 1 Active on Alarm
System Input Phs Rotation Error 10002 1 Active on Alarm
System Input Current Limit 10003 1 Active on Alarm
System Input Current Imbalance 10004 1 Active on Alarm
Bypass
Bypass Not Available 10015 1 Active on Alarm
Bypass Overload Phase A 10016 1 Active on Alarm
Bypass Overload Phase B 10017 1 Active on Alarm
Bypass Overload Phase C 10018 1 Active on Alarm
Bypass Auto Retransfer Failed 10019 1 Active on Alarm
Bypass Static Switch Overload 10020 1 Active on Alarm
Bypass Static Switch Unavailable 10021 1 Active on Alarm
Bypass Auto Transfer Failed 10022 1 Active on Alarm
Bypass Frequency Error 10023 1 Active on Alarm
Bypass - Manual Rexfr Inhibited 10024 1 Active on Alarm
Bypass - Manual Xfr Inhibited 10025 1 Active on Alarm
Battery
Battery Automatic Test Inhibited 10036 1 Active on Alarm
Battery Capacity Low 10037 1 Active on Alarm
Battery Discharging 10038 1 Active on Alarm
Battery Temperature Imbalance 10039 1 Active on Alarm
Battery Equalize 10040 1 Active on Alarm
Battery Auto Test In Progress 10041 1 Active on Alarm
Main Battery Disconnect Open 10042 1 Active on Alarm
Battery Low 10043 1 Active on Alarm
Battery Temperature Sensor Fault 10044 1 Active on Alarm
Battery Circuit Breaker 1 Open 10045 1 Active on Alarm
Battery Circuit Breaker 2 Open 10046 1 Active on Alarm
Battery Circuit Breaker 3 Open 10047 1 Active on Alarm
Battery Circuit Breaker 4 Open 10048 1 Active on Alarm
Battery Circuit Breaker 5 Open 10049 1 Active on Alarm
Battery Circuit Breaker 6 Open 10050 1 Active on Alarm
Battery - External Monitor 1 10051 1 Active on Alarm
Battery - External Monitor 2 10052 1 Active on Alarm
Battery Ground Fault 10053 1 Active on Alarm
Battery Over Temperature Limit 10054 1 Active on Alarm
Battery Low Shutdown 10055 1 Active on Alarm
Battery Over Temperature 10056 1 Active on Alarm
Battery Test Failed 10057 1 Active on Alarm
Unexpected Main Battery Disconnect Closure 10058 1 Active on Alarm
Battery Over Voltage 10059 1 Active on Alarm
Battery Fuse Fault 10060 1 Active on Alarm
Main Battery Disconnect Forced To Unlock 10061 1 Active on Alarm
Battery Test Manually Stopped 10062 1 Active on Alarm
Battery Test Passed 10063 1 Active on Alarm
DC Bus