Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 168
Table 58 Liebert NXL
™
- 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status Coil
Number
of Bits Notes / Units
Input
System Input Power Problem 10001 — 1 Active on Alarm
System Input Phs Rotation Error 10002 — 1 Active on Alarm
System Input Current Limit 10003 — 1 Active on Alarm
System Input Current Imbalance 10004 — 1 Active on Alarm
Bypass
Bypass Not Available 10015 — 1 Active on Alarm
Bypass Overload Phase A 10016 — 1 Active on Alarm
Bypass Overload Phase B 10017 — 1 Active on Alarm
Bypass Overload Phase C 10018 — 1 Active on Alarm
Bypass Auto Retransfer Failed 10019 — 1 Active on Alarm
Bypass Static Switch Overload 10020 — 1 Active on Alarm
Bypass Static Switch Unavailable 10021 — 1 Active on Alarm
Bypass Auto Transfer Failed 10022 — 1 Active on Alarm
Bypass Frequency Error 10023 — 1 Active on Alarm
Bypass - Manual Rexfr Inhibited 10024 — 1 Active on Alarm
Bypass - Manual Xfr Inhibited 10025 — 1 Active on Alarm
Battery
Battery Automatic Test Inhibited 10036 — 1 Active on Alarm
Battery Capacity Low 10037 — 1 Active on Alarm
Battery Discharging 10038 — 1 Active on Alarm
Battery Temperature Imbalance 10039 — 1 Active on Alarm
Battery Equalize 10040 — 1 Active on Alarm
Battery Auto Test In Progress 10041 — 1 Active on Alarm
Main Battery Disconnect Open 10042 — 1 Active on Alarm
Battery Low 10043 — 1 Active on Alarm
Battery Temperature Sensor Fault 10044 — 1 Active on Alarm
Battery Circuit Breaker 1 Open 10045 — 1 Active on Alarm
Battery Circuit Breaker 2 Open 10046 — 1 Active on Alarm
Battery Circuit Breaker 3 Open 10047 — 1 Active on Alarm
Battery Circuit Breaker 4 Open 10048 — 1 Active on Alarm
Battery Circuit Breaker 5 Open 10049 — 1 Active on Alarm
Battery Circuit Breaker 6 Open 10050 — 1 Active on Alarm
Battery - External Monitor 1 10051 — 1 Active on Alarm
Battery - External Monitor 2 10052 — 1 Active on Alarm
Battery Ground Fault 10053 — 1 Active on Alarm
Battery Over Temperature Limit 10054 — 1 Active on Alarm
Battery Low Shutdown 10055 — 1 Active on Alarm
Battery Over Temperature 10056 — 1 Active on Alarm
Battery Test Failed 10057 — 1 Active on Alarm
Unexpected Main Battery Disconnect Closure 10058 — 1 Active on Alarm
Battery Over Voltage 10059 — 1 Active on Alarm
Battery Fuse Fault 10060 — 1 Active on Alarm
Main Battery Disconnect Forced To Unlock 10061 — 1 Active on Alarm
Battery Test Manually Stopped 10062 — 1 Active on Alarm
Battery Test Passed 10063 — 1 Active on Alarm
DC Bus