BACnet Communications - Thermal Management Products
297 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 96 Liebert DataMate
™
, Liebert Mini-Mate2
™
- MM2
Controller MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Data Description
BACnet Instance Notes
Status Points (View)
Temperature BS01_x —
Humidity BS02_x —
Cooling BS03_x 1=On / 0=Off
Heating BS04_x 1=On / 0=Off
Humidification BS05_x 1=On / 0=Off
Dehumidification BS06_x 1=On / 0=Off
Econ-o-Cycle BS07_x 1=On / 0=Off
Stages BS08_x —
% Capacity BS09_x —
Unit On/Off BS18_x 1=On / 0=Off
Alarm Points
Communications BA01_x:00 —
Local Off BA01_x:01 —
Remote Off BA01_x:02 —
High Head Pressure 1 BA01_x:03 —
Loss of Airflow BA01_x:05 —
Standby Glycol Unit On BA01_x:06 —
Change Filters BA01_x:07 —
High Temperature BA01_x:08 —
Low Temperature BA01_x:09 —
High Humidity BA02_x:00 —
Low Humidity BA02_x:01 —
Humidifier Problem BA02_x:02 —
Smoke Detected BA02_x:08 —
Loss of Water Flow BA02_x:09 —
Standby Unit On BA02_x:10 —
Short Cycle BA03:01 —
Loss of Power BA03:02 —
Local Alarm 1 BA03:06 —
Local Alarm 2 BA03:07 —
High Water BA03:08 —
Local Alarm 4 BA03:09 —
Setpoints (View)
Temperature BS10_x —
Humidity BS12_x —
Control Points (Set)
Remote On/Off BC01_x Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint BC02_x —
Humidity Setpoint BC03_x —