Modbus 485 and Modbus IP Protocols - Thermal Management Products
91 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Setpoints (View)
Return Air Temperature 40016 1 10 deg C (R/W)
Return Air Humidity 40017 1 10 deg C (R/W)
Supply Air Temperature 40018 1 10 deg C (R/W)
High Temp Alarm 40025 1 10 deg C (R/W)
Low Temp Alarm 40026 1 10 deg C (R/W)
High Hum Alarm 40027 1 10 % (R/W)
Low Hum Alarm 40028 1 10 % (R/W)
Restart Delay 40029 1 Seconds (R/W)
Control Points (Set)
Activation Mode 40006 1 1=On / 0=Off (R/W)
General Alarm Status 40022 1 1=On / 0=Off; write 0 to reset alarm
Audible Alarm Status 40023 1 1=On / 0=Off; write 0 to ack alarm
Return Air Temperature 40349 1 10 deg C (R/W)
Return Air Humidity 40350 1 10 deg C (R/W)
Supply Air Temperature 40351 1 10 deg C (R/W)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 31 Liebert Atlas Air
, Liebert Atlas PEC
, Liebert LECS 15
- Input and Holding - C10 2-step
Controller C10
Liebert Products
Liebert Atlas Air
Liebert Atlas PEC
Liebert LECS 15
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units