BACnet Communications - UPS Systems
299 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
4.3 UPS Systems
Table 98 Liebert APM
™
, Liebert NXC
™
, Liebert NXR
™
- Binary Data
Data Label
Object Type Instance
Object
Name Access Notes
System Status
Battery Auto Test In Progress Binary_Value 1 4172_1 RD Active on Alarm
Battery Equalize Binary_Value 2 4170_1 RD Active on Alarm
Battery Charging Inhibited Binary_Value 3 4200_1 RD Active on Alarm
On Generator Binary_Value 4 4315_1 RD Active on Alarm
System Events
System Input Power Problem Binary_Value 15 4122_1 RD Active on Alarm
Rectifier Failure Binary_Value 16 4295_1 RD Active on Alarm
Inverter Failure Binary_Value 17 4233_1 RD Active on Alarm
Bypass Not Available Binary_Value 18 4135_1 RD Active on Alarm
Battery Low Binary_Value 19 4162_1 RD Active on Alarm
LBS Inhibited Binary_Value 20 4758_1 RD Active on Alarm
System Fan Failure Binary_Value 21 4311_1 RD Active on Alarm
Equipment Over Temperature Binary_Value 22 4310_1 RD Active on Alarm
System Shutdown - EPO Binary_Value 23 4213_1 RD Active on Alarm
Bypass Static Switch Unavailable Binary_Value 24 4143_1 RD Active on Alarm
Bypass - Excess Auto Retransfers Binary_Value 25 4139_1 RD Active on Alarm
Parallel Comm Warning Binary_Value 26 4823_1 RD Active on Alarm
Power Supply Failure Binary_Value 27 4314_1 RD Active on Alarm
Battery Over Temperature Binary_Value 28 4219_1 RD Active on Alarm
System Input Phs Rotation Error Binary_Value 29 4146_1 RD Active on Alarm
Fuse Failure Binary_Value 30 4440_1 RD Active on Alarm
Inverter Overload Phase A Binary_Value 31 4234_1 RD Active on Alarm
Inverter Overload Phase B Binary_Value 32 4235_1 RD Active on Alarm
Inverter Overload Phase C Binary_Value 33 4236_1 RD Active on Alarm
MMS Overload Binary_Value 34 4831_1 RD Active on Alarm
Inverter Shutdown - Overload Binary_Value 35 4290_1 RD Active on Alarm
System Output Fault Binary_Value 36 4389_1 RD Active on Alarm
Internal Communications Failure Binary_Value 37 4300_1 RD Active on Alarm
Battery Charging Error Binary_Value 38 4164_1 RD Active on Alarm
System Input Current Imbalance Binary_Value 39 4382_1 RD Active on Alarm
Main Battery Disconnect Open Binary_Value 40 4173_1 RD Active on Alarm
Inverter Static Switch SCR Short Binary_Value 41 4391_1 RD Active on Alarm
Battery Not Qualified Binary_Value 42 5149_1 RD Active on Alarm
Battery Terminals Reversed Binary_Value 43 5150_1 RD Active on Alarm
Battery Converter Failure Binary_Value 44 5151_1 RD Active on Alarm
Inverter SCR Open Binary_Value 45 5152_1 RD Active on Alarm
Load Sharing Fault Binary_Value 46 5153_1 RD Active on Alarm
DC Bus Abnormal Binary_Value 47 5154_1 RD Active on Alarm
Mains Input Neutral Lost Binary_Value 48 5155_1 RD Active on Alarm
Load Impact Transfer Binary_Value 49 5156_1 RD Active on Alarm
User Operation Invalid Binary_Value 50 5157_1 RD Active on Alarm