Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - UPS Systems
351 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Ratings
Input Isolation Transformer MultiState_Value 109 4266_1 RD
1 = Not Installed
2 = Installed
Device Status
Backfeed Breaker MultiState_Value 120 4764_1 RD
1 = Open
2 = Close
3 = Not Installed
SBS Load Disconnect MultiState_Value 121 4765_1 RD
1 = Open
2 = Close
3 = Not Installed
Input Breaker MultiState_Value 122 4766_1 RD
1 = Open
2 = Close
3 = Not Installed
Trap Filter Disconnect MultiState_Value 123 4767_1 RD
1 = Open
2 = Close
3 = Not Installed
Output Breaker MultiState_Value 124 4768_1 RD
1 = Open
2 = Close
3 = Not Installed
Internal Bypass Breaker MultiState_Value 125 4769_1 RD
1 = Open
2 = Close
3 = Not Installed
Bypass Isolation Breaker MultiState_Value 126 4770_1 RD
1 = Open
2 = Close
3 = Not Installed
Maintenance Bypass Breaker MultiState_Value 127 4772_1 RD
1 = Open
2 = Close
3 = Not Installed
Maintenance Isolation Breaker MultiState_Value 128 4773_1 RD
1 = Open
2 = Close
3 = Not Installed
Output Series Static Switch MultiState_Value 129 4774_1 RD
1 = Off
2 = On
3 = Not Installed
Module Output Breaker MultiState_Value 130 4775_1 RD
1 = Open
2 = Close
3 = Not Installed
MultiModule
Module Output Breaker for Module 1 MultiState_Value 141 4836_1 RD
1 = Open
2 = Close
3 = Not Installed
Module Output Breaker for Module 2 MultiState_Value 142 4837_1 RD
1 = Open
2 = Close
3 = Not Installed
Module Output Breaker for Module 3 MultiState_Value 143 4838_1 RD
1 = Open
2 = Close
3 = Not Installed
Module Output Breaker for Module 4 MultiState_Value 144 4839_1 RD
1 = Open
2 = Close
3 = Not Installed
Module Output Breaker for Module 5 MultiState_Value 145 4840_1 RD
1 = Open
2 = Close
3 = Not Installed
Module Output Breaker for Module 6 MultiState_Value 146 4841_1 RD
1 = Open
2 = Close
3 = Not Installed
Table 112 Liebert NXL
- 50 Hz, CE version (Models 48 and 49)—Multistate Data
Data Label
Object Type Instance Object Name Access Notes