Modbus 485 and Modbus IP Protocols - UPS Systems
163 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 57 Liebert NXL
™
- 60Hz, UL version (Model 40) - Glossary
Data Label Data Description
Auto Restart In Progress Auto restart is in progress
Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be
cleared and auto retransfer from the bypass to the inverter can take place
Automatic Restart Failed Automatic restart failed
Backfeed Breaker Open The backfeed breaker is in the open position
Backfeed Breaker Backfeed breaker
Battery - External Monitor 1 External battery monitor 1 - battery maintenance required
Battery - External Monitor 2 External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This Discharge Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed Cumulative battery amp-hours withdrawn over the life of the battery
Battery Capacity Low Battery capacity is low
Battery Cell Count - Lead Acid Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium Battery cell count - nickel cadmium
Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal
Battery Charging Reduced-Extrnl Using a reduced battery charging algorithm due to an external signal
Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open Battery circuit breaker 6 is open
Battery Circuit Breaker 7 Open Battery circuit breaker 7 is open
Battery Circuit Breaker 8 Open Battery circuit breaker 8 is open
Battery Commission Date Date and time when battery placed into service
Battery Discharge Power Instantaneous battery power while discharging
Battery Discharge Time The time on battery operation for this discharge
Battery Discharging The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage
level.
Battery Ground Fault Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date The date and time of the last battery discharge
Battery Low Shutdown Battery disconnect due to end-of-discharge.
Battery Low
The calculated battery time remaining has reached the low battery
threshold
Battery Over Temperature A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge The percentage of battery charge
Battery Self Test Battery self test is in progress
Battery Temperature for Cabinet The battery temperature for a cabinet
Battery Temperature Imbalance Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault A battery temperature sensor fault has been detected
Battery Test Failed Battery test failed
Battery Test Inhibited Automatic (scheduled) battery tests are inhibited
Battery Time Remaining The calculated available time on battery