Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 194
Table 65 Liebert Series 300
™
UPS - Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Automatic Restart Enabled 10001 1 1 — —
Battery Charge Compensation 10046 — 1 — —
Inverter Ready 10047 — 1 — —
Load Circuit 1 State 10057 — 1 — —
Load Circuit 2 State 10058 — 1 — —
Load Circuit 3 State 10059 — 1 — —
Load Circuit 4 State 10060 — 1 — —
Load Circuit 5 State 10061 — 1 — —
Load Circuit 6 State 10062 — 1 — —
Load Circuit 7 State 10063 — 1 — —
Load Circuit 8 State 10064 — 1 — —
Load Circuit 9 State 10065 — 1 — —
Load Circuit 10 State 10066 — 1 — —
Load Circuit 11 State 10067 — 1 — —
Load Circuit 12 State 10068 — 1 — —
Load Circuit 13 State 10069 — 1 — —
Load Circuit 14 State 10070 — 1 — —
Load Circuit 15 State 10071 — 1 — —
Load Circuit 16 State 10072 — 1 — —
Load On Inverter 10073 — 1 — —
Bypass Active 10074 — 1 — —
Buck On 10076 — 1 — —
Replace Battery 10081 — 1 — —
Battery Under Test 10082 — 1 — —
Load On Battery 10128 — 1 — —
Low Battery - Shutdown Imminent 10152 — 1 — —
Output Overload 10154 — 1 — —
Over Temperature Warning 10171 — 1 — —
Battery Over Temperature CB Trip 10172 — 1 — —
Input Power Supply Fail 10186 — 1 — —
Input Over Voltage 10187 — 1 — —
Input Under Voltage 10188 — 1 — —
Bad Input Frequency 10190 — 1 — —
Bypass Input Voltage/Frequency Fault 10202 — 1 — —
Output Under Voltage 10218 — 1 — —
Output Over Voltage 10219 — 1 — —
Battery Charger Fail 10234 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.