Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 88
Table 30 Liebert Mini-Mate2
™
8 Ton - Input and Holding - L8T
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature — 40001 1 — —
Humidity — 40002 1 — —
Cooling — 40003 1 — 1=On / 0=Off
Heating — 40004 1 — 1=On / 0=Off
Humidification — 40005 1 — 1=On / 0=Off
De-humidification — 40006 1 — 1=On / 0=Off
Econ-O-Cycle — 40007 1 — 1=On / 0=Off
Stages — 40008 1 — —
% Capacity — 40009 1 — —
Analog input 1 — 40023 1 —
A/D raw value w/ slope =1
and offset = 0
Analog input 2 — 40024 1 —
A/D raw value w/ slope =1
and offset = 0
Analog input 3 — 40025 1 —
A/D raw value w/ slope =1
and offset = 0
Analog input 4 — 40026 1 —
A/D raw value w/ slope =1
and offset = 0
Alarm Points
Communications — 40289 1 — Bit 0
Local Off — 40289 1 — Bit 1
Remote Off — 40289 1 — Bit 2
High Head Pressure 1 — 40289 1 — Bit 3
High Head Pressure 2 — 40289 1 — Bit 4
Loss of Airflow — 40289 1 — Bit 5
Standby Glycol Unit On — 40289 1 — Bit 6
Not Used — 40289 1 — Bit 7
Change Filters — 40289 1 — Bit 8
High Temperature — 40289 1 — Bit 9
Low Temperature — 40289 1 — Bit 10
High Humidity — 40290 1 — Bit 0
Low Humidity — 40290 1 — Bit 1
Humidifier Problem — 40290 1 — Bit 2
Smoke Detected — 40290 1 — Bit 8
Loss of Water — 40290 1 — Bit 9
Standby Unit On — 40290 1 — Bit 10
Not Used — 40291 1 — Bit 0
Short Cycle — 40291 1 — Bit 1
Loss of Power — 40291 1 — Bit 2
Local Alarm 1 — 40291 1 — Bit 6
Local Alarm 2 — 40291 1 — Bit 7