Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 182
Table 60 Liebert NXL
™
- 50Hz, CE version (Models 48 and 49) - Glossary
Data Label Data Description
Auto Restart In Progress Auto restart is in progress
Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be cleared and auto
retransfer from the bypass to the inverter can take place
Automatic Restart Failed Automatic restart failed
Backfeed Breaker Open The backfeed breaker is in the open position
Backfeed Breaker Backfeed breaker
Battery - External Monitor 1 External battery monitor 1 - battery maintenance required
Battery - External Monitor 2 External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This
Discharge
Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed Cumulative battery amp-hours withdrawn over the life of the battery
Battery Auto Test In Progress Automatic battery test is in progress
Battery Automatic Test Inhibited Automatic (scheduled) battery tests are inhibited
Battery Capacity Low Battery capacity is low
Battery Cell Count - Lead Acid Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium Battery cell count - nickel cadmium
Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open Battery circuit breaker 6 is open
Battery Discharge Power Instantaneous battery power while discharging
Battery Discharge Time The time on battery operation for this discharge
Battery Discharging The battery is discharging
Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level.
Battery Fuse Fault One or more battery fuse faults has occurred.
Battery Ground Fault Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date The date and time of the last battery discharge
Battery Low Shutdown The battery voltage has dropped to the End of Discharge value.
Battery Low The calculated battery time remaining has reached the low battery threshold
Battery Over Temperature Limit A battery temperature sensor is reporting a value above a predetermined limit.
Battery Over Temperature A battery temperature sensor is reporting a value above a threshold
Battery Over Voltage
The system has detected that the battery voltage has exceeded a predetermined
limit.
Battery Percentage Charge The percentage of battery charge
Battery SCR Status The status of the battery SCR.
Battery Temperature for Cabinet The battery temperature for a cabinet
Battery Temperature Imbalance Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault A battery temperature sensor fault has been detected
Battery Test Failed Battery test failed
Battery Test Manually Stopped The battery test was manually stopped prior to completion
Battery Test Passed Battery test passed