Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 144
Input Current L1 30154 — 1 — A
Input Power Factor L1 30155 — 1 100 —
Bypass Voltage L1 30159 — 1 — V
Output Voltage L1 30163 — 1 — V
Output Current L1 30164 — 1 — A
Output Load L1 30165 — 1 — —
Output Power Factor L1 30166 — 1 100 %
Apparent Output Power L1 30168 — 2 — VA
Reactive Output Power L1 30170 — 2 — VAR
Output Power L1 30172 — 2 — W
Output Current Crest Factor L1 30186 — 1 — %
Input Voltage L2-L3 30201 — 1 — V
Input Voltage L2 30203 — 1 — V
Input Current L2 30204 — 1 — A
Input Power Factor L2 30205 — 1 100 —
Bypass Voltage L2 30209 — 1 — V
Output Voltage L2 30213 — 1 — V
Output Current L2 30214 — 1 — A
Output Load L2 30215 — 1 — %
Output Power Factor L2 30216 — 1 100 —
Apparent Output Power L2 30218 — 2 — VA
Reactive Output Power L2 30220 — 2 — VAR
Output Power L2 30222 — 2 — W
Output Current Crest Factor L2 30236 — 1 — %
Input Voltage L3-L1 30251 — 1 — V
Input Voltage L3 30253 — 1 — V
Input Current L3 30254 — 1 — A
Input Power Factor L3 30255 — 1 100 —
Bypass Voltage L3 30259 — 1 — V
Output Voltage L3 30263 — 1 — V
Output Current L3 30264 — 1 — A
Output Load L3 30265 — 1 — %
Output Power Factor L3 30266 — 1 100 —
Apparent Output Power L3 30268 — 2 — VA
Reactive Output Power L3 30270 — 2 — VAR
Output Power L3 30272 — 2 — W
Output Current Crest Factor L3 30286 — 1 — %
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 53 Liebert NX
™
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units