Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 54
System Operations
Return Fluid Temperature 30491 1 10
Units: deg C
Int16
1, 2
Return Fluid Temperature 30492 1 10
Units: deg F
Int16
1, 2
Supply Fluid Temperature 30493 1 10
Units: deg C
Int16
1, 2
Supply Fluid Temperature 30494 1 10
Units: deg F
Int16
1, 2
Actual Supply Fluid Temp Set Point 30495 1 10
Units: deg C
Int16
1, 2
Actual Supply Fluid Temp Set Point 30496 1 10
Units: deg F
Int16
1, 2
Condenser Inlet Water Temperature 30497 1 10
Units: deg C
Int16
1, 2
Condenser Inlet Water Temperature 30498 1 10
Units: deg F
Int16
1, 2
Condenser Outlet Water Temperature 30499 1 10
Units: deg C
Int16
1, 2
Condenser Outlet Water Temperature 30500 1 10
Units: deg F
Int16
1, 2
Supply Heated Water Temp Set Point 30501 40501 1
Units: deg C
Int16
1, 2
Supply Heated Water Temp Set Point 30502 40502 1
Units: deg F
Int16
1, 2
Free Cooling Utilization 30503 1
Units: %
Uint16
1, 2
Reheat Utilization 30504 1
Units: %
Uint16
1, 2
Compressor Utilization 30505 1
Units: %
Uint16
1, 2
Ambient Air Temperature 30506 1 10
Units: deg C
Int16
1, 2
Ambient Air Temperature 30507 1 10
Units: deg F
Int16
1, 2
Compressor Economizer Utilization 30508 1
Units: %
Uint16
1, 2
Condenser Adiabatic Cooling Utilization 30509 1
Units: %
Uint16
1, 2
Pump 1 State 30510 1
0 = off
1 = on
1, 2
Pump 2 State 30511 1
0 = off
1 = on
1, 2
System Events
System Event Acknowledge/Reset 40515 1
2 = Reset
4 = Acknowledge
1, 2
Time
System Date and Time 39998 49998 2 Secs since Epoch (UTC) 1, 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 15 Liebert HPC
(Chiller) - Input and Holding (continued)
Controller Liebert iCOM
®
v4
Data Label
Input Holding
# of
Reg Scale Notes/Units
Extra
Notes