BACnet Communications - UPS Systems
307 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
PowerModule 1
Power Module Fan Fault Binary_Value 99 5838_1 RD Active on Alarm
Power Module Over Temperature Binary_Value 100 5839_1 RD Active on Alarm
Power Module Shutdown - Over Temperature Binary_Value 101 5840_1 RD Active on Alarm
PowerModule 2
Power Module Fan Fault Binary_Value 112 5838_2 RD Active on Alarm
Power Module Over Temperature Binary_Value 113 5839_2 RD Active on Alarm
Power Module Shutdown - Over Temperature Binary_Value 114 5840_2 RD Active on Alarm
PowerModule 10
Power Module Fan Fault Binary_Value 216 5838_10 RD Active on Alarm
Power Module Over Temperature Binary_Value 217 5839_10 RD Active on Alarm
Power Module Shutdown - Over Temperature Binary_Value 218 5840_10 RD Active on Alarm
BatteryModule 1
Battery Module Temperature Sensor Fault Binary_Value 229 5847_1 RD Active on Alarm
Battery Module Over Temperature Binary_Value 230 5848_1 RD Active on Alarm
Replace Battery Module Binary_Value 231 5849_1 RD Active on Alarm
BatteryModule 2
Battery Module Temperature Sensor Fault Binary_Value 242 5847_2 RD Active on Alarm
Battery Module Over Temperature Binary_Value 243 5848_2 RD Active on Alarm
Replace Battery Module Binary_Value 244 5849_2 RD Active on Alarm
BatteryModule 80
Battery Module Temperature Sensor Fault Binary_Value 1256 5847_80 RD Active on Alarm
Battery Module Over Temperature Binary_Value 1257 5848_80 RD Active on Alarm
Replace Battery Module Binary_Value 1258 5849_80 RD Active on Alarm
ChargerModule
Charger Module Fan Fault Binary_Value 1269 5842_1 RD Active on Alarm
Table 102 Liebert APS
™
- Binary Data (continued)
Data Label
Object Type Instance
Object
Name Access Notes