Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
117 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Load Over-current 40292 1 Bit 13
Ground Over-current 40292 1 Bit 14
Neutral Over-current 40292 1 Bit 15
Customer Alarm #1 40293 1 Bit 0
Customer Alarm #2 40293 1 Bit 1
Customer Alarm #3 40293 1 Bit 2
Customer Alarm #4 40293 1 Bit 3
Customer Alarm #5 40293 1 Bit 4
Customer Alarm #6 40293 1 Bit 5
Customer Alarm #7 40293 1 Bit 6
Customer Alarm #8 40293 1 Bit 7
Neutral Current 1 Over Limit 40294 1 Bit 13 (4P Only)
Neutral Current 2 Over Limit 40294 1 Bit 14 (4P Only)
Neutral Snubber Fail 40294 1 Bit 15 (4P Only)
Neutral 1 SCR Short 40295 1 Bit 0 (4P Only)
Neutral 2 SCR Short 40295 1 Bit 1 (4P Only)
Neutral 1 SCR Open 40295 1 Bit 2 (4P Only)
Neutral 2 SCR Open 40295 1 Bit 3 (4P Only)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 39 Liebert STS2
, Liebert STS2/PDU
- Input and Holding - STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units