Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 128
System Output Apparent Power L1 30473 — 1 100
Units : kVA
Uint 16
System Output Apparent Power L2 30474 — 1 100
Units : kVA
Uint 16
System Output Power 30475 — 1 100
Units : kW
Uint 16
System Output Power L1 30476 — 1 100
Units : kW
Uint 16
System Output Power L2 30477 — 1 100
Units : kW
Uint 16
System Output Pct Power L1 30478 — 1 10
Units : %
Uint 16
System Output Pct Power L2 30479 — 1 10
Units : %
Uint 16
Output Qualification Status 30480 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Maximum Load Alarm Limit 30481 40481 1 10
Units : kVA
Uint16
Shutdown After Delay 30482 40482 1 —
Units : sec
Uint 16
Reboot After Delay 30483 40483 1 —
Units : sec
Uint 16
Output On Delay 30484 40484 1 —
Units : sec
Uint 16
Inverter
Inverter On/Off State 30495 — 1 —
0 = off
1 = on
System Set To Operate With 30496 40496 1 —
0 = No Redundancy
1 = Redundancy
System Capacity 30507 — 1 1000
Units : kVA
Uint 16
Frame Capacity 30508 — 1 1000
Units : kVA
Uint 16
Number of Installed Power Modules 30509 — 1 — Uint 16
Number Of Active Power Modules 30510 — 1 — Uint 16
Number Of Power Modules With Warnings 30511 — 1 — Uint 16
Number Of Failed Power Modules 30512 — 1 — Uint 16
Number of Installed Battery Strings 30513 — 1 — Uint 16
Number of Active Battery Strings 30514 — 1 — Uint 16
Number of Battery Strings With Warnings 30515 — 1 — Uint 16
Number of Failed Battery Strings 30516 — 1 — Uint 16
UPS Output Source 30517 — 1 —
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Status 30518 — 1 —
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
Table 44 Liebert APS
™
- Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units