Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
171 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input Holding # of Reg Scale Notes/Units
Input
System Input RMS A-B 30385 1 10
Units : VAC
Uint16
System Input RMS B-C 30386 1 10
Units : VAC
Uint16
System Input RMS C-A 30387 1 10
Units : VAC
Uint16
System Input RMS Current Phase A 30388 1
Units : A AC
Uint16
System Input RMS Current Phase B 30389 1
Units : A AC
Uint16
System Input RMS Current Phase C 30390 1
Units : A AC
Uint16
System Input Frequency 30391 1 100
Units : Hz
Uint16
Input Qualification Status 30392 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Bypass
Bypass Input Voltage RMS A-B 30403 1 10
Units : VAC
Uint16
Bypass Input Voltage RMS B-C 30404 1 10
Units : VAC
Uint16
Bypass Input Voltage RMS C-A 30405 1 10
Units : VAC
Uint16
Bypass Input Frequency 30406 1 100
Units : Hz
Uint16
Bypass Sync Phase Difference 30407 1
Units : deg
Int16
Bypass SS Overload Time Remain 30408 1
Units : sec
Uint16
Static Bypass Switch 30409 1
0 = off
1 = on
Bypass Qualification Status 30410 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Auto Retransfer Time Remaining 30411 1
Units : sec
Uint16
Battery
Battery Total Discharge Time 30422 1
Units : hr
Uint16
Battery Percentage Charge 30423 1 Uint16
Battery Volts at Main Disconnect 30424 1
Units : VDC
Uint16
Battery Volts for Cabinet 1 30425 1
Units : VDC
Uint16
Battery Volts for Cabinet 2 30426 1
Units : VDC
Uint16
Battery Volts for Cabinet 3 30427 1
Units : VDC
Uint16