BACnet Communications - BACnet Protocol Implementation Conformance Statement
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 218
Analog Object
Units
Possible values of the Units property include the BACnet Engineering Units defined in the BACnet
standard, plus these additional proprietary units values:
Analog Object
Property
Analog
Input
Analog
Output
Analog
Value Comments
Object_Identifier x x x
Object_Name x x x
Object_Type x x x
Present_Value x x x
Writable if any of these conditions apply:
Object is Analog Output
Object is Analog Value and associated device Data Description is
writable
Out_Of_Service is True
Description x x x
Status_Flags x x x
Event_State x x x
Reliability x x x
Out_Of_Service x x x Writable. Values: True/False. Default: False.
Units x x x See Units below this table.
Priority_Array x (x) Support for this property on Analog Value objects is device-dependent.
Relinquish_Default x (x)
Support for this property on Analog Value objects is device-dependent.
The value is equal to the Present_Value so that if all entries in the
Priority_Array are relinquished, the Present_Value does not change.
COV_Increment x x x Writable. Default: 0.5.
Value Units
256 Ampere-Hours
257 MilliHertz (.001 Hertz)
258 GigaHertz (1,000,000,000 Hertz)
259 PSI - Absolute
260 Total Harmonic Distortion (%)
261 Microhms (.000001 Ohms)