Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 114
Table 39 Liebert STS2
, Liebert STS2/PDU
- Input and Holding - STS2
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Total Transfer Count 40001 1
Preferred Source 40002 1 1=Source 1, 2=Source 2
Active Source 40003 1 1=Source 1, 2=Source 2
Source 1 Volts A-B 40004 1 V
Source 1 Volts B-C 40005 1 V
Source 1 Volts C-A 40006 1 V
Source 1 Current A 40007 1 A
Source 1 Current B 40008 1 A
Source 1 Current C 40009 1 A
Source 1 Frequency 40010 1 10 Hz
Source 2 Volts A-B 40011 1 V
Source 2 Volts B-C 40012 1 V
Source 2 Volts C-A 40013 1 V
Source 2 Current A 40014 1 A
Source 2 Current B 40015 1 A
Source 2 Current C 40016 1 A
Source 2 Frequency 40017 1 10 Hz
Output kW 40018 1 kW
Output kVA 40019 1 kVA
CB 1 Status 40024 1 Bit 0
CB 2 Status 40024 1 Bit 1
CB 3 Status 40024 1 Bit 2
CB 3A Status 40024 1 Bit 3
CB 4 Status 40024 1 Bit 4
CB 5 Status 40024 1 Bit 5
CB Spare 1 Status 40024 1 Bit 6
CB Spare 2 Status 40024 1 Bit 7
CB 7 Status 40024 1 Bit 8
CB 8 Status 40024 1 Bit 9
Auto Xfer Enabled 40025 1 Bit 0
Has Dual Out Breakers 40025 1 Bit 1
Has PDU Equipped 40025 1 Bit 2
Has 4 pole Switch 40025 1 Bit 3
Has Shunt Trip 40025 1 Bit 4
Has Wye Out Xfmr 40025 1 Bit 5
Has Rmt Sorce Sel 40025 1 Bit 6
Manual I peak Reset 40025 1 Bit 7
Auto Restart Enabled 40025 1 Bit 8