Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 206
Equipment Over Temperature 40290 1
Bit 0
Any of Battery / Heatsink / Ambient / Timeout
Shutdown
Battery Ground Fault CB Trip 40290 1 Bit 1
Power Supply Fail 40290 1
Bit 2
Any of Input / Bypass / Output / F1 / SWGR /
MM / Option / AuEPO / LBS Power Fail
EPO Shutdown 40290 1 Bit 3
Rectifier Fail 40290 1 Bit 4
Inverter Fail 40290 1 Bit 5
Hardware Shutdown 40290 1 Bit 6
Battery Discharge 40290 1 Bit 7
Input Current Imbalance 40290 1 Bit 8
Input Line fail 40290 1 Bit 9
Input Under Voltage 40290 1 Bit 10
Input Over Voltage 40290 1 Bit 11
Input Over Current 40290 1 Bit 12
Battery CB Open 40290 1 Bit 13
Battery Sync Error 40290 1 Bit 14
Bypass Voltage Out of Tolerance 40290 1 Bit 15
Bypass Line Fail 40291 1 Bit 0
Inverter Over Current 40291 1 Bit 1
Output OF/UF 40291 1 Bit 2
Inverter Overload 40291 1
Bit 3
Any of Inverter Phase A / B / C Overload
Excessive Auto Retransfer 40291 1 Bit 4
Equipment Over Temperature
Warning
40291 1
Bit 5
Any of AuBattery / Ambient / Heatsink / Inlet
Over Temp Warning
Fan Fail 40291 1
Bit 6
Any of Power Pole Fan 1 / 2 / 3, Primary Fan 1
/ 2 / 3 and System Fan Fail
SBS Unable 40291 1 Bit 7
Inverter Off By User 40291 1 Bit 8
Battery low Warning 40291 1 Bit 9
Battery Test Fail 40291 1 Bit 10
User Shutdown 40291 1 Bit 11
Load On Bypass 40291 1 Bit 12
Input Contact Alarms 40291 1
Bit 13
Any of Input Contact 1-8 Alarms
Generic Alarms 40291 1
Bit 14
Any other alarm conditions that are not
mapped
Bypass Overload 40291 1
Bit 15
Any of Bypass A / B / C Overload
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 73 Liebert Npower
- Input and Holding - IMP (continued)
Controller Single Module Series - SMS
Liebert Products Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units