Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 272
Fluid - Supply (Outlet) Fluid
Supply Fluid Over Temp Binary_Value 84 4645_1_1 RD Active on Alarm 1, 2
Supply Fluid Under Temp Binary_Value 85 4648_1_1 RD Active on Alarm 1, 2
Supply Fluid Temp Sensor Issue Binary_Value 86 4651_1_1 RD Active on Alarm 1, 2
Pumps
All Pumps Loss of Flow Binary_Value 97 5297_1 RD Active on Alarm 1, 2
Pump 1 Loss of Flow Binary_Value 98 4656_1 RD Active on Alarm 1, 2
Pump 2 Loss of Flow Binary_Value 99 4659_1 RD Active on Alarm 1, 2
Pumps - Pump 1
Pump Hours Exceeded Binary_Value 110 5300_1_1 RD Active on Alarm 1, 2
Pumps - Pump 2
Pump Hours Exceeded Binary_Value 121 5300_1_2 RD Active on Alarm 1, 2
Free Cooling
Free Cooling Valve Hours Exceeded Binary_Value 132 5306_1 RD Active on Alarm 1, 2
Ambient Air Temperature Sensor Issue Binary_Value 133 4618_1 RD Active on Alarm 1, 2
Evaporators
Evaporator Inlet Temp Sensor Issue Binary_Value 144 5308_1 RD Active on Alarm 1, 2
Evaporator Return Fluid Over Temp Binary_Value 145 5559_1 RD Active on Alarm 1, 2
Evaporator Return Fluid Under Temp Binary_Value 146 5560_1 RD Active on Alarm 1, 2
Evaporators - Evaporator 1
Evaporator Fluid Freeze - Auto Reset Binary_Value 157 5310_1_1 RD Active on Alarm 1, 2
Evaporator Fluid Freeze - Manual Reset
Required
Binary_Value 158 5311_1_1 RD Active on Alarm 1, 2
Supply Refrigerant Temp Sensor Issue Binary_Value 159 4640_1_1 RD Active on Alarm 1, 2
Evaporators - Evaporator 2
Evaporator Fluid Freeze - Auto Reset Binary_Value 170 5310_1_2 RD Active on Alarm 1, 2
Evaporator Fluid Freeze - Manual Reset
Required
Binary_Value 171 5311_1_2 RD Active on Alarm 1, 2
Supply Refrigerant Temp Sensor Issue Binary_Value 172 4640_1_2 RD Active on Alarm 1, 2
System Events
Customer Input 1 Binary_Value 183 4270_1 RD Active on Alarm 1, 2
Customer Input 2 Binary_Value 184 4271_1 RD Active on Alarm 1, 2
Customer Input 3 Binary_Value 194 4272_1 RD Active on Alarm 2
Customer Input 4 Binary_Value 195 4273_1 RD Active on Alarm 2
Unit On Binary_Value 185 5109_1 RD Active on Alarm 1, 2
Unit Off Binary_Value 186 5110_1 RD Active on Alarm 1, 2
Master Unit Communication Lost Binary_Value 187 5120_1 RD Active on Alarm 1, 2
Subgroup Event Occurred During
Communication Loss
Binary_Value 188 5315_1 RD Active on Alarm 1, 2
Humidifier Control Board Not Detected Binary_Value 189 5045_1 RD Active on Alarm 1, 2
RAM Battery Issue Binary_Value 190 5119_1 RD Active on Alarm 1, 2
Unit Code Missing Binary_Value 191 5418_1 RD Active on Alarm 1, 2
Unspecified General Event Binary_Value 192 5588_1 RD Active on Alarm 2
Unit Shutdown Unspecified General Event Binary_Value 193 5775_1 RD Active on Alarm 2
EEV 1
EEV Unspecified General Event Binary_Value 200 5625_1 RD Active on Alarm 2
Table 87 Liebert HPC
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes
Extra
Notes