Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 152
System Output Pct Power Phase A 30165 — 1 — %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs A 30166 — 1 100 —
N+1, 1+N,
1+1, SMS
System Input RMS B-C 30201 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase B 30204 — 1 — A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS B-C 30207 — 1 — VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS B-C 30211 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS B-N 30212 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs B 30214 — 1 — A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase B 30215 — 1 — %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs B 30216 — 1 100 —
N+1, 1+N,
1+1, SMS
System Input RMS C-A 30251 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase C 30254 — 1 — A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS C-A 30257 — 1 — VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS C-A 30261 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS C-N 30262 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs C 30264 — 1 — A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase C 30265 — 1 — %
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs C 30266 — 1 100 —
N+1, 1+N,
1+1, SMS
Battery Discharge Time 30309 — 1 — sec
N+1, 1+N,
1+1, SMS
Battery Amp-Hours Consumed This
Discharge
30310 — 1 — AH
N+1, 1+N,
1+1, SMS
Input Qualification Status 30312 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
Bypass Sync Phase Difference 30313 — 1 — deg
SCC, 1+N,
1+1, SMS
Bypass SS Overload Time Remain 30314 — 1 — sec
SCC, 1+N,
1+1, SMS
Bypass Qualification Status 30315 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
SCC, 1+N,
1+1, SMS
Table 56 Liebert NXL
™
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types