BACnet Communications - UPS Systems
331 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
System Isolation Output
Breaker (IOB)
MultiState_Value 155 4854_1 RD
1 = Open
2 = Close
3 = Not Installed
SCC
SCC Event Summary MultiState_Value 156 4855_1 RD
1 = None
2 = Alarm
3 = Fault
SCC
MMS UPS Battery Status MultiState_Value 157 4873_1 RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
1+N, N+1
MMS UPS Output Source MultiState_Value 158 4874_1 RD
1 = Other
2 = off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
1+N, SCC
ModuleList 1
MMS Inter-Module Comm
Status
MultiState_Value 169 4856_1 RD
1 = Failed
2 = Normal
1+N, SCC
MMS Event Summary MultiState_Value 170 4857_1 RD
1 = None
2 = Alarm
3 = Fault
1+N, SCC
MMS Module Inverter Status MultiState_Value 171 4858_1 RD
1 = off
2 = on
1+N
MMS Module Output Voltage
Status
MultiState_Value 172 4859_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
1+N, SCC
MMS Module Output Source MultiState_Value 173 4860_1 RD
1 = off
2 = Normal
3 = Bypass
4 = Maintenance
Bypass
1+N, SCC
ModuleList 2
MMS Inter-Module Comm
Status
MultiState_Value 184 4856_2 RD
1 = Failed
2 = Normal
1+N, SCC
MMS Event Summary MultiState_Value 185 4857_2 RD
1 = None
2 = Alarm
3 = Fault
1+N, SCC
MMS Module Inverter Status MultiState_Value 186 4858_2 RD
1 = off
2 = on
1+N
MMS Module Output Voltage
Status
MultiState_Value 187 4859_2 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
1+N, SCC
MMS Module Output Source MultiState_Value 188 4860_2 RD
1 = off
2 = Normal
3 = Bypass
4 = Maintenance
Bypass
1+N, SCC
ModuleList 8
MMS Inter-Module Comm
Status
MultiState_Value 274 4856_8 RD
1 = Failed
2 = Normal
1+N, SCC
MMS Event Summary MultiState_Value 275 4857_8 RD
1 = None
2 = Alarm
3 = Fault
1+N, SCC
Table 108 Liebert NXL
™
- 60Hz, UL version (Model 40) - Multistate Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type