Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 78
Table 24 Liebert DS
and Liebert PeX
- Input and Holding
Controller Liebert iCOM
®
v3
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Vendor ID 30001 40001 1
Device ID 30002 40002 1
Version Number 30003 40003 1
UPS/Env/Pwr 30004 40004 1
Timer Mode
1
30016 40016 1
Type of DT Room-FC
2
30017 40017 1
Humidity Control
3
30018 40018 1
VSD Setpoint 30019 40019 1 % (HP)
Supply Temperature Limit 30020 40020 1 10 deg C
DT between Room and FC 30021 40021 1 10 deg C
Minimum CW Temperature 30022 40022 1 10 deg C
Temperature Setpoint 30023 40023 1 10 deg C
Temperature Proportional Band 30024 40024 1 10 deg C
Temperature Deadband 30025 40025 1 10 deg C
Temperature Integration Time 30026 40026 1 Minutes
Humidity Setpoint 30027 40027 1 %
Humidity Proportional Band 30028 40028 1 %
Humidity Integration Time 30029 40029 1 Minutes
Humidity Deadband 30030 40030 1 %
Single Unit Auto-Restart Delay 30031 40031 1 Seconds
Infrared Flush Rate 30032 40032 1 %
Temp Control Type
4
30033 40033 1
Sleep Interval 1 Start Time Hour: Minute 30040 40040 1 LSB:Min
Sleep Interval 1 End Time Hour: Minute 30041 40041 1 LSB:Min
Sleep Interval 2 Start Time Hour: Minute 30042 40042 1 LSB:Min
Sleep Interval 2 End Time Hour: Minute 30043 40043 1 LSB:Min
Timer Deadband 30044 40044 1 10 deg C
Manual VSD Timer/Counter
5
30045 40045 1
High Temperature 30050 40050 1 10 deg C
Low Temperature 30051 40051 1 10 deg C
High Temperature Sensor A 30052 40052 1 10 deg C
Low Temperature Sensor A 30053 40053 1 10 deg C
High Humidity 30054 40054 1 %
Low Humidity 30055 40055 1 %
High Humidity Sensor A 30056 40056 1 %
Low Humidity Sensor A 30057 40057 1 %
Fan Run Hour Threshold 30070 40070 Hours
Compressor 1 Run Hour Threshold 30071 40071 Hours
Compressor 2 Run Hour Threshold 30072 40072 Hours
Humidifier Run Hours Threshold 30073 40073 Hours
Dehumidification Run Hours Threshold 30074 40074 Hours
CW/FC Run Hours Threshold 30075 40075 Hours