BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 298
Table 97 Liebert Mini-Mate2
™
8 Ton - L8T
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Data Description
BACnet Instance Notes
Status Points (View)
Temperature BS01_x —
Humidity BS02_x —
Cooling BS03_x 1=On / 0=Off
Heating BS04_x 1=On / 0=Off
Humidification BS05_x 1=On / 0=Off
De-humidification BS06_x 1=On / 0=Off
Econ-O-Cycle BS07_x 1=On / 0=Off
Stages BS08_x —
% Capacity BS09_x —
Unit Status (On / Off) BS18_x 1=On / 0=Off
Alarm Points
Communications BA01_x:00 —
Local Off BA01_x:01 —
Remote Off BA01_x:02 —
High Head Pressure 1 BA01_x:03 —
High Head Pressure 2 BA01_x:04 —
Loss of Airflow BA01_x:05 —
Standby Glycol Unit On BA01_x:06 —
Change Filters BA01_x:08 —
High Temperature BA01_x:09 —
Low Temperature BA01_x:10 —
High Humidity BA02_x00 —
Low Humidity BA02_x01 —
Humidifier Problem BA02_x02 —
Smoke Detected BA02_x:08 —
Loss of Water BA02_x:09 —
Standby Unit On BA02_x:10 —
Short Cycle BA03_x:01 —
Loss of Power BA03_x:02 —
Local Alarm 1 BA03_x:06 —
Local Alarm 2 BA03_x:07 —
High Water Humidifier Pan BA03_x:08 —
Setpoints (View)
Temperature Setpoint BS10_x —
Humidity Setpoint BS12_x —
Control Points (Set)
Unit On / Off BC01_x Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint BC02_x -
Temperature Tolerance BC02_x Multiply desired value by 1000
Humidity Setpoint BC03_x -
Humidity Tolerance BC03_x Multiply desired value by 1000
Reheat Lockout BC01_x Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout BC01_x Bit 4 on=HL off Bit 5 on=HL on