Modbus 485 and Modbus IP Protocols - Thermal Management Products
71 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
XD System 16 Secondary Fans
Fan State 31557 — — —
0 = off
1 = on
2 = economy
Fan Economy Mode 31558 41558 1 —
0 = disabled
1 = automatic
2 = manual
XD System 17 Temperature Sensor 1
Remote Sensor Temperature 31564 — 1 10 Units : deg C
Remote Sensor Temperature 31565 — 1 10 Units : deg F
XD System 17 Temperature Sensor 2
Remote Sensor Temperature 31571 — 1 10 Units : deg C
Remote Sensor Temperature 31572 — 1 10 Units : deg F
XD System 17 Temperature Sensor 4
Remote Sensor Temperature 31585 — 1 10 Units : deg C
Remote Sensor Temperature 31586 — 1 10 Units : deg F
XD System 17 Secondary Fans
Fan State 31592 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31593 41593 1 —
0 = disabled
1 = automatic
2 = manual
XD System 18 Temperature Sensor 1
Remote Sensor Temperature 31599 — 1 10 Units : deg C
Remote Sensor Temperature 31600 — 1 10 Units : deg F
XD System 18 Temperature Sensor 2 —
Remote Sensor Temperature 31606 — 1 10 Units : deg C
Remote Sensor Temperature 31607 — 1 10 Units : deg F
XD System 18 Temperature Sensor 4
Remote Sensor Temperature 31620 — 1 10 Units : deg C
Remote Sensor Temperature 31621 — 1 10 Units : deg F
XD System 18 Secondary Fans
Fan State 31627 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31628 41628 1 —
0 = disabled
1 = automatic
2 = manual
XD System 19 Temperature Sensor 1
Remote Sensor Temperature 31634 — 1 10 Units : deg C
Remote Sensor Temperature 31635 — 1 10 Units : deg F
XD System 19 Temperature Sensor 2
Remote Sensor Temperature 31641 — 1 10 Units : deg C
Remote Sensor Temperature 31642 — 1 10 Units : deg F
XD System 19 Temperature Sensor 4
Remote Sensor Temperature 31655 — 1 10 Units : deg C
Remote Sensor Temperature 31656 — 1 10 Units : deg F
Table 21 Liebert XDP
™
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units