Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 130
BatteryModule 2
Module Operating Status 30670 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage 30671 1 10
Units : VDC
Uint16
Battery Module Temperature 30672 1 10
Units : deg C
Int16
Battery Module Temperature 30673 1 10
Units : degF
Int16
Number of Discharge Cycles 30674 1 Uint 16
Accumulated Discharge Time 30675 1 10
Units : hr
Uint 16
BatteryModule 80
Module Operating Status 31918 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage 31919 1 10
Units : VDC
Uint16
Battery Module Temperature 31920 1 10
Units : deg C
Int16
Battery Module Temperature 31921 1 10
Units : degF
Int16
Number of Discharge Cycles 31922 1 Uint 16
Accumulated Discharge Time 31923 1 10
Units : hr
Uint 16
ChargerModule
Module Operating Status 31934 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Charger Mode 31935 1
0 = Not Charging
1 = Float Charging
2 = Current Limit
Charging
3 = Equalize Charging
BypassControlModule
Module Operating Status 31946 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
System Configuration
System Date and Time 31957 41957 2 Secs since Epoch(UTC)
SystemConfiguration
System Date and Time 39998 49998 2 Secs since Epoch(UTC)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 44 Liebert APS
- Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units