Modbus 485 and Modbus IP Protocols - UPS Systems
137 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 47 Liebert GXT2
™
and Liebert GXT3
™
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 — Bits 12 - 15
Number of Bypass Lines 30004 40004 1 — Bits 4 - 7
Number of Output Lines 30004 40004 1 — Bits 8 - 11
Number of SubModules 30009 40009 1 — —
Load Circuit Present 30013 40013 1 —
There are 16 possible Load
Circuits. Each bit represents 1
Load Circuit. Load Circuit 1 is bit 0,
Load Circuit 2 is bit 1 and so on. If
the bit is 1, then the Load Circuit is
supported.
Battery Cabinet Type 30018 40018 2 — —
Battery Cabinet Number 30019 40019 1 — —
Battery AmpHour 30020 40020 1 — AH
Nominal Power Rating 30021 40021 2 — VA
Nominal Input Voltage 30027 40027 1 — V
Nominal Output Voltage 30028 40028 1 — V
Nominal Static Bypass Switch Voltage 30029 40029 1 — V
Nominal Input Current 30030 40030 1 — A
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 —
Nominal Battery Voltage 30034 40034 1 — V
Auto Restart Delay 30051 40051 1 — Seconds
Device Low Battery Time 30053 40053 1 — Minutes
Load (Apparent Power) 30102 — 2 — VA
Load (Real Power) 30104 — 2 — W
Load / Capacity 30106 — 1 — %
Input Frequency 30107 — 1 10 Hz
Output Frequency 30108 — 1 10 Hz
Bypass Frequency 30109 — 1 10 Hz
Battery Charge Status 30112 — 1 —
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 — 1 — V
Battery Time Remaining 30115 — 1 — Minutes
Battery Charge Percentage 30116 — 1 — %
Ambient Temperature 30119 — 1 — deg C
Battery Test Result 30130 — 1 —
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1 30153 — 1 — V
Bypass Voltage L1 30159 — 1 — V
Output Voltage L1 30163 — 1 — V