Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
263 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Event Configuration
System Event Acknowledge/Reset MultiState_Value 171 4717_1 WO
1 = Reset
2 = Acknowledge
Smoke Detected - Event Control MultiState_Value 172 4721_1 RW
1 = disabled
2 = enabled
Smoke Detected - Event Type MultiState_Value 173 4722_1 RW
1 = Message
2 = Warning
3 = Alarm
Water Under Floor - Event Control MultiState_Value 174 4724_1 RW
1 = disabled
2 = enabled
Water Under Floor - Event Type MultiState_Value 175 4725_1 RW
1 = Message
2 = Warning
3 = Alarm
Customer Input 1 - Event Control MultiState_Value 176 4718_1 RW
1 = disabled
2 = enabled
Customer Input 1 - Event Type MultiState_Value 177 4719_1 RW
1 = Message
2 = Warning
3 = Alarm
Customer Input 2 - Event Control MultiState_Value 178 5098_1 RW
1 = disabled
2 = enabled
Customer Input 2 - Event Type MultiState_Value 179 5099_1 RW
1 = Message
2 = Warning
3 = Alarm
Customer Input 3 - Event Control MultiState_Value 180 5100_1 RW
1 = disabled
2 = enabled
Customer Input 3 - Event Type MultiState_Value 181 5101_1 RW
1 = Message
2 = Warning
3 = Alarm
Customer Input 4 - Event Control MultiState_Value 182 5102_1 RW
1 = disabled
2 = enabled
Customer Input 4 - Event Type MultiState_Value 183 5103_1 RW
1 = Message
2 = Warning
3 = Alarm
Service Required - Event Control MultiState_Value 184 4727_1 RW
1 = disabled
2 = enabled
Service Required - Event Type MultiState_Value 185 4728_1 RW
1 = Message
2 = Warning
3 = Alarm
Shutdown - Loss Of Power - Event
Control
MultiState_Value 186 4715_1 RW
1 = disabled
2 = enabled
Shutdown - Loss Of Power - Event Type MultiState_Value 187 4716_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Loss of Flow - Event Control MultiState_Value 188 5082_1 RW
1 = disabled
2 = enabled
Ext Loss of Flow - Event Type MultiState_Value 189 5083_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Reheat Lockout - Event Control MultiState_Value 190 5084_1 RW
1 = disabled
2 = enabled
Table 85 Liebert CRV
- Multistate Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes