Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
143 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 53 Liebert NX
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 Bits 8 - 11
Number of SubModules 30009 40009 1
Module Number 30014 40014 1
Device Module Count 30015 40015 1
Device Redundant Count 30016 40016 1
Device Module Mode 30017 40017 1
Nominal Power Rating 30021 40021 2 VA
Nominal Input Voltage 30027 40027 1 V
Nominal Output Voltage 30028 40028 1 V
Nominal Static Bypass Switch Voltage 30029 40029 1 V
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal DC Bus #1 Voltage 30035 40035 1 V
Nominal DC Bus #2 Voltage 30036 40036 1
Nominal Battery Float Voltage 30038 40038 1 V
Load Bus Sync Mode 30040 40040 1
Auto Restart Delay 30051 40051 1 Seconds
Device Low Battery Time 30053 40053 1 Minutes
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Bypass Frequency 30109 1 10 Hz
Battery Charge Status 30112 1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 1 V
Battery Current (Charge/Discharge) 30114 1 A
Battery Time Remaining 30115 1 Minutes
Battery Charge Percentage 30116 1 %
Battery Temperature 30117 1 C
Ambient Temperature 30119 1 C
Parallel Load Source 30128 1
Rotary Breaker 30129 1
Battery Test Result 30130 1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2 30151 1 V
Input Voltage L1 30153 1 V