Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
259 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 84 Liebert CRV
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes
Air Temperature
Supply Air Temperature Analog_Value 1 5002_1 RD Units: deg C
Supply Air Temperature Analog_Value 10001 5002_1_deg_F RD Units: deg F
Return Air Temperature Analog_Value 2 4291_1 RD Units: deg C
Return Air Temperature Analog_Value 10002 4291_1_deg_F RD Units: deg F
Return Dew Point Analog_Value 3 5004_1 RD Units: deg C
Return Dew Point Analog_Value 10003 5004_1_deg_F RD Units: deg F
Remote Sensor Minimum Temperature Analog_Value 4 5005_1 RD Units: deg C
Remote Sensor Minimum Temperature Analog_Value 10004 5005_1_deg_F RD Units: deg F
Remote Sensor Maximum Temperature Analog_Value 5 5006_1 RD Units: deg C
Remote Sensor Maximum Temperature Analog_Value 10005 5006_1_deg_F RD Units: deg F
Remote Sensor Average Temperature Analog_Value 6 5007_1 RD Units: deg C
Remote Sensor Average Temperature Analog_Value 10006 5007_1_deg_F RD Units: deg F
Air Temperature Set Point Analog_Value 7 5008_1 RW Units: deg C
Air Temperature Set Point Analog_Value 10007 5008_1_deg_F RW Units: deg F
Cooling Proportional Band Analog_Value 8 5009_1 RW Units: deg C
Cooling Proportional Band Analog_Value 10008 5009_1_deg_F RW Units: deg F
Heating Proportional Band Analog_Value 9 5010_1 RW Units: deg C
Heating Proportional Band Analog_Value 10009 5010_1_deg_F RW Units: deg F
Air Temperature Dead Band Analog_Value 10 5011_1 RW Units: deg C
Air Temperature Dead Band Analog_Value 10010 5011_1_deg_F RW Units: deg F
Supply Air Over Temp Threshold Analog_Value 11 5014_1 RW Units: deg C
Supply Air Over Temp Threshold Analog_Value 10011 5014_1_deg_F RW Units: deg F
Supply Air Under Temp Threshold Analog_Value 12 5018_1 RW Units: deg C
Supply Air Under Temp Threshold Analog_Value 10012 5018_1_deg_F RW Units: deg F
Return Air Over Temp Threshold Analog_Value 13 5022_1 RW Units: deg C
Return Air Over Temp Threshold Analog_Value 10013 5022_1_deg_F RW Units: deg F
Humidity
Supply Humidity Analog_Value 24 5027_1 RD Units: % RH
Return Humidity Analog_Value 25 5028_1 RD Units: % RH
Humidity Set Point Analog_Value 26 5029_1 RW Units: % RH
Humidification Proportional Band Analog_Value 27 5030_1 RW Units: % RH
Dehumidification Proportional Band Analog_Value 28 5031_1 RW Units: % RH
Humidity Dead Band Analog_Value 29 5032_1 RW Units: % RH
High Return Humidity Threshold Analog_Value 30 5033_1 RW Units: % RH
Low Return Humidity Threshold Analog_Value 31 5035_1 RW Units: % RH
Fans
Fan Speed Proportional Band Analog_Value 42 5048_1 RW Units: deg C
Fan Speed Proportional Band Analog_Value 10042 5048_1_deg_F RW Units: deg F
Fan Speed Manual Set Point Analog_Value 43 5049_1 RW Units: %
Fan Speed Maximum Set Point Analog_Value 44 5050_1 RW Units: %
Fan Speed Minimum Set Point Analog_Value 45 5051_1 RW Units: %