Modbus 485 and Modbus IP Protocols - Thermal Management Products
87 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Setpoints (View)
Temperature — 40010 1 — —
Temp Tolerance — 40011 1 — —
Humidity — 40012 1 — —
Humidity Tolerance — 40013 1 — —
High Temperature Alarm — 40014 1 — —
Low Temperature Alarm — 40015 1 — —
High Humidity Alarm — 40016 1 — —
Low Humidity Alarm — 40017 1 — —
Chill Water Flush Rate — 40025 1 — Hours (R/W)
Auto Restart Delay — 40026 1 — 0.1 minute (R/W)
Control Points (Set)
Unit On/Off — 40018 1 — 1=On / 0=Off (R/W)
Remote On/Off — 40349 1 —
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint — 40350 1 — (W)
Temperature Tolerance — 40350 1 1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Humidity Setpoint — 40351 1 - (W)
Humidity Tolerance — 40351 1 1000
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Trendable Points (Set)
Temperature — — 1 — —
Humidity — — 1 — —
Reports
Trend — — 1 — —
Status — — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 29 Liebert DataMate
™
, Liebert Mini-Mate2
™
- Input and Holding - MM2 (continued)
Controller MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units