Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
69 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
XD System 10 Secondary Fans
Fan State 31347 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31348 41348 1
0 = disabled
1 = automatic
2 = manual
XD System 11 Temperature Sensor 1
Remote Sensor Temperature 31354 1 10 Units : deg C
Remote Sensor Temperature 31355 1 10 Units : deg F
XD System 11 Temperature Sensor 2
Remote Sensor Temperature 31361 1 10 Units : deg C
Remote Sensor Temperature 31362 1 10 Units : deg F
XD System 11 Temperature Sensor 4
Remote Sensor Temperature 31375 1 10 Units : deg C
Remote Sensor Temperature 31376 1 10 Units : deg F
XD System 11 Secondary Fans
Fan State 31382 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31383 41383 1
0 = disabled
1 = automatic
2 = manual
XD System 12 Temperature Sensor 1
Remote Sensor Temperature 31389 1 10 Units : deg C
Remote Sensor Temperature 31390 1 10 Units : deg F
XD System 12 Temperature Sensor 2
Remote Sensor Temperature 31396 1 10 Units : deg C
Remote Sensor Temperature 31397 1 10 Units : deg F
XD System 12 Temperature Sensor 4
Remote Sensor Temperature 31410 1 10 Units : deg C
Remote Sensor Temperature 31411 1 10 Units : deg F
XD System 12 Secondary Fans
Fan State 31417 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31418 41418 1
0 = disabled
1 = automatic
2 = manual
XD System 13 Temperature Sensor 1
Remote Sensor Temperature 31424 1 10 Units : deg C
Remote Sensor Temperature 31425 1 10 Units : deg F
XD System 13 Temperature Sensor 2
Remote Sensor Temperature 31431 1 10 Units : deg C
Remote Sensor Temperature 31432 1 10 Units : deg F
XD System 13 Temperature Sensor 4
Remote Sensor Temperature 31445 1 10 Units : deg C
Remote Sensor Temperature 31446 1 10 Units : deg F
Table 21 Liebert XDP
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units