BACnet Communications - Thermal Management Products
257 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Remote Sensors 10
Remote Sensor Issue Binary_Value 151 5060_10 RD Active on Alarm
Compressor
Compressor 1 High Head Pressure Binary_Value 162 4669_1 RD Active on Alarm
Compressor 1 Low Suction Pressure Binary_Value 163 5062_1 RD Active on Alarm
Compressor 1 Hours Exceeded Binary_Value 164 5063_1 RD Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue Binary_Value 165 5064_1 RD Active on Alarm
Dig Scroll Comp 1 Over Temp Binary_Value 166 5065_1 RD Active on Alarm
Compressor 1 Low Pressure Transducer Issue Binary_Value 167 5066_1 RD Active on Alarm
Compressor 1 High Pressure Transducer Issue Binary_Value 168 5148_1 RD Active on Alarm
Ext Compressor Lockout Binary_Value 169 5067_1 RD Active on Alarm
Compressor 1 Short Cycle Binary_Value 170 4681_1 RD Active on Alarm
Compressor 1 Pump Down Issue Binary_Value 171 5146_1 RD Active on Alarm
Reheater
Reheater Over Temperature Binary_Value 182 5068_1 RD Active on Alarm
Electric Reheater Hours Exceeded Binary_Value 183 5069_1 RD Active on Alarm
Ext Reheat Lockout Binary_Value 184 5070_1 RD Active on Alarm
Condenser
Condenser 1 Issue Binary_Value 195 5071_1 RD Active on Alarm
Condenser VFD Issue Binary_Value 196 5072_1 RD Active on Alarm
Condenser TVSS Issue Binary_Value 197 5073_1 RD Active on Alarm
Chilled Water
Supply Chilled Water Over Temp Binary_Value 208 4626_1 RD Active on Alarm
Chilled Water Control Valve Position Binary_Value 209 4703_1 RD Active on Alarm
Supply Chilled Water Loss of Flow Binary_Value 210 4980_1 RD Active on Alarm
System Events
Customer Input 1 Binary_Value 221 4270_1 RD Active on Alarm
Customer Input 2 Binary_Value 222 4271_1 RD Active on Alarm
Customer Input 3 Binary_Value 223 4272_1 RD Active on Alarm
Customer Input 4 Binary_Value 224 4273_1 RD Active on Alarm
Smoke Detected Binary_Value 225 4720_1 RD Active on Alarm
Water Under Floor Binary_Value 226 4723_1 RD Active on Alarm
Service Required Binary_Value 227 4726_1 RD Active on Alarm
Shutdown - Loss Of Power Binary_Value 228 4714_1 RD Active on Alarm
Ext Over Temperature Binary_Value 229 5104_1 RD Active on Alarm
Ext Loss of Flow Binary_Value 230 5105_1 RD Active on Alarm
Ext Condenser Pump High Water Binary_Value 231 5106_1 RD Active on Alarm
Ext Standby Glycol Pump On Binary_Value 232 5107_1 RD Active on Alarm
External Fire Detected Binary_Value 233 5108_1 RD Active on Alarm
Unit On Binary_Value 234 5109_1 RD Active on Alarm
Unit Off Binary_Value 235 5110_1 RD Active on Alarm
Unit Standby Binary_Value 236 5111_1 RD Active on Alarm
Table 83 Liebert CRV
™
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes