BACnet Communications - UPS Systems
311 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Auto Restart Minimum Battery Setting MultiState_Value 64 5832_1 RW
1 = 0%
2 = 10%
3 = 20%
4 = 30%
5 = 40%
6 = 50%
7 = 60%
8 = 70%
9 = 80%
10 = 90%
PowerModule 1
Module Operating Status MultiState_Value 75 5833_1 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status MultiState_Value 76 5864_1 RD
1 = Inverter Inactive
2 = Inverter Active
PowerModule 2
Module Operating Status MultiState_Value 87 5833_2 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status MultiState_Value 88 5864_2 RD
1 = Inverter Inactive
2 = Inverter Active
PowerModule 10
Module Operating Status MultiState_Value 183 5833_10 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Inverter Status MultiState_Value 184 5864_10 RD
1 = Inverter Inactive
2 = Inverter Active
BatteryModule 1
Module Operating Status MultiState_Value 195 5834_1 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fau
BatteryModule 2
Module Operating Status MultiState_Value 206 5834_2 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
BatteryModule 80
Module Operating Status MultiState_Value 1064 5834_80 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
ChargerModule
Module Operating Status MultiState_Value 1075 5835_1 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Charger Mode MultiState_Value 1076 5841_1 RD
1 = Not Charging
2 = Float Charging
3 = Current Limit Charging
4 = Equalize Charging
BypassControlModule
Module Operating Status MultiState_Value 1087 5836_1 RD
1 = Normal
2 = Warning
3 = Alarm
4 = Fault
Table 104 Liebert APS
™
- Multistate Data (continued)
Data Label
Object Type Instance Object Name Access Notes