Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
25 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Instantaneous Power 1 30860 1 - W 6
Instantaneous Power 2 30861 1 W 6
Instantaneous Power 3 30862 1 W 6
Instantaneous Power 4 30863 1 W 6
Instantaneous Power 5 30864 1 W 6
Instantaneous Power 6 30865 1 W 6
Energy Consumption 1 30870 40870 2 kWH 6
Energy Consumption 2 30872 40872 2 kWH 6
Energy Consumption 3 30874 40874 2 kWH 6
Energy Consumption 4 30876 40876 2 kWH 6
Energy Consumption 5 30878 40878 2 kWH 6
Energy Consumption 6 30880 40880 2 kWH 6
Fluid Input Temperature 1 30900 1 10 deg C 6
Fluid Input Temperature 2 30901 1 10 deg C 6
Fluid Input Temperature 1 30902 1 10 deg F 6
Fluid Input Temperature 2 30903 1 10 deg F 6
Fluid Output Temperature 1 30906 1 10 deg F 6
Fluid Output Temperature 2 30907 1 10 deg F 6
Fluid Flow Rate 1 30908 2 10 l/min 6
Fluid Flow Rate 2 30910 2 10 l/min 6
Unit Cooling Load 31001 2 10 kW 6
Circuit Cooling Load 31003 2 10 kW 6
System Date and Time 39998 49998 2 1, 2, 3, 4, 5, 6
Table 9 Extra notes key to Table 8
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes