Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 226
Low Static Pressure Binary_Value 565 5631_1 RD Active on Alarm 3, 5, 6
Static Pressure Sensor Out of Range Binary_Value 566 5910_1 RD Active on Alarm 5, 6
EconoPhase
Pump Unspecified General Event Binary_Value 623 5636_1 RD Active on Alarm 4, 5
Global Condensers - GC Unit 1
Condenser Unit Unspecified General
Event
Binary_Value 643 5637_1_1 RD Active on Alarm 3, 4, 5, 6
Global Condensers - GC Circuit 1
Condenser Circuit Unspecified
General Event
Binary_Value 644 5638_1_1 RD Active on Alarm 3, 4, 5, 6
Power Measurement 1
Input Undervoltage Binary_Value 1001 5568_1 RD Active on Alarm 6
Power Measurement 2
Input Undervoltage Binary_Value 1002 5568_2 RD Active on Alarm 6
Power Measurement 6
Input Undervoltage Binary_Value 1006 5568_6 RD Active on Alarm 6
Fluid 1
Fluid Temperature Sensor Issue Binary_Value 1021 5911_1 RD Active on Alarm 6
Fluid Flow Sensor Issue Binary_Value 1022 5912_1 RD Active on Alarm 6
Fluid 2
Fluid Temperature Sensor Issue Binary_Value 1031 5911_2 RD Active on Alarm 6
Fluid Flow Sensor Issue Binary_Value 1032 5912_2 RD Active on Alarm 6
Table 77 Extra Notes to Table 76
Number Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 76 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes